E+E Elektronik Serie EE45 Bedienungsanleitung Seite 3

Kondensationswächter

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

1.
MOUNTING LOCATION:
condensation. The mounting surface must be clean, dry and bare (i.e. uninsulated).
2.
REMOVING OF THE PROTECTIVE FILM:
3. a) PIPE / DUCT MOUNTING:
max Ø 30mm
b) WALL MOUNTING:
For mounting on flat surfaces use two screws (M4, not included in the scope of supply).
47
i
Important: When mounting make sure that that a good thermal contact between the sensor and the surface is ensured.
4.
ELECTRICAL CONNECTION:
Pull-Up
EE45
electronics
5.
SELF-HELP IN CASE OF ERRORS:
error:
possible cause:
EE45 doesn´t switch
- wrong mounting
(switching point cannot
- insufficient thermal contact
be reached)
- pollution
complete failure of the
- no supply voltage
instrument
INSTALLATION OF EE45:
The sensor should be mounted to that part of the pipe or of the wall which is most susceptible to the formation of
Remove the protective film on the heat-conductive film before mounting.
Use the elastic metal link chain supplied with the shippment for pipe / duct mounting.
metal link chain
32
U
V
R
V
OUT+ (white)
OUT- (yellow)
24V AC ±20%
(green)
VI
24V COM
(brown)
min Ø 15mm
Pull-Down
EE45
electronics
VI
remedies:
- when the mounting is loose tighten the screws resp. the metal link chain
- if necessary remove the protective film on the heat-conductive film or
tighten the screws resp. the metal link chain
- cleaning
- check the supply cable and supply voltage
3
heat-conductive film
metal link chain
heat-conductive film
16
U D C
U
V
V
1 2 V
2 4 V
3 0 V
OUT+ (white)
OUT- (yellow)
24V AC ±20%
R
V
(green)
24V COM
(brown)
R
V
> 1k 1
> 2k 4
> 3k 0

Werbung