Herunterladen Diese Seite drucken

Warranty Conditions - PEHA PHC 2 Installations- Und Bedienungsanleitung

Eingangstaster

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

PEHA Elektro GmbH & Co. KG
Postfach 1727 • D-58467 Lüdenscheid • Tel.: (02351)185-0 • Fax: (02351)27666 • e-mail: peha@peha.de • Internet: www.peha.de
InsTaLLaTIon anD oPeraTIng InsTrucTIon
Phc 2/4/8-fold input pushbutton
940/8.xx eT(b); 940/4.xx eT(b); 940/2.xx eT(b)
aPPLIcaTIon
The PHC input pushbutton is used to execute switching procedures in a PHC system
and to display switch statuses. The LED of a button can be switched ON and OFF by
the PHC system without additional wiring (status display).
There is a labelling button on the front side. The illumination intensity of the labelling
area can be adjusted (optional).
notes:
– Detailed expert knowledge for programming a PHC system
are required.
– The PHC-functions for the PHC system are to be programmed
with the PHC system software (see PHC manual).
– Read through the operating instructions carefully before putting
the device into service.
DIsPosaL oF The DeVIce
Do not dispose of old devices in the household waste! The device must be
disposed of in compliance with the laws and standards of the country in which
it is operated! The device contains electrical components that must be disposed
of as electronics waste. The enclosure is made from recyclable plastic.

warranTy conDITIons

These operating instructions are an integral part of both the device and our terms of
warranty. They must be handed over to the user. The technical design of the appliance
is subject to change without prior notification. PEHA products are manufactured
and quality-checked with the latest technology according to applicable national and
international regulations. Nevertheless, if a product should exhibit a defect, PEHA
warrants to make remedy as follows (regardless of any claims against the dealer to
which the end user may be entitled as a result of the sales transaction):
In the event of a justified and properly established claim, PEHA shall exercise its
prerogative to either repair or replace the defective device. Further claims or liability
for consequential damage are explicitly excluded. A justifiable deficiency is deemed to
exist if the device exhibits a structural, manufacturing, or material defect that makes it
unusable or substantially impairs its utility at the time it is turned over to the end user.
The warranty does not apply to natural wear, improper usage, incorrect connection,
device tampering or the effects of external influences. The warranty period is 24 months
from the date of purchase by the end user from a dealer and ends not later than 36
months after the device's date of manufacture. German law shall be applicable for the
settlement of warranty claims.
saFeTy
This device is only intended to be used for its stated application. Unauthorised
conversions, modifications or changes are not permissible!
This device may not be used in conjunction with other devices whose operation could
present a hazard to persons, animals or property.
The following must be observed:
• Prevailing statutes, standards and regulations.
• State-of-the-art technology at the time of installation.
• The PHC manual, the operating instructions of the PHC modules.
• Operating instructions can only cite general stipulations. These are to
be viewed in the context of a specific system.
The following systems may not be switched:
• Safety switches such as EMERGENCY OFF
• Emergency power supplies
• Fire alarm systems
• Emergency lighting systems
TechnIcaL sPecIFIcaTIons
Power supply Phc
Nom. 24 V DC (SELV)
system (Phc bus)
21-28V DC (ripple voltage 5 %)
6 mA
own consumption
+ 0,8 mA per LED
+ 6 mA for illumination (optional)
Input module bus
Input connector (24V, A+, B-, 0V)
coding
DIP switch, 8-pin (module address)
Test specifications
EN 50428
Identification
CE
Protection level
IP20
PEHA_M_940-8-4-2.xx ET(B) (Rev02_130306)
All manuals and user guides at all-guides.com
gb
31060000-163
sTrucTure anD DescrIPTIon
Phc 8-fold input pushbutton (art. no.: 940/8.xx eT(b))
T1
L1
L5
T2
L2
L6
L9
T3
L3
L7
T4
L4
L8
Labelling area with button function
(illumination L9 optional)
Phc 4-fold input pushbutton (art. no.: 940/8.xx eT(b))
L1
L5
T1
L2
L6
L9
L3
L7
T2
L4
L8
Labelling area with button function
(illumination L9 optional)
Phc 2-fold input pushbutton (art. no.: 940/8.xx eT(b))
L1
L5
L2
L6
L9
T1
L3
L7
L4
L8
Labelling area with button function
(illumination L9 optional)
InsTaLLaTIon anD commIssIonIng
safety information
Installation and commissioning may only be done by an authorised electrician. Mains
power (230 V ~/50 Hz) to electrical equipment must be switched off during installation.
Applicable laws and standards of the country in which the device is operated must
be observed!
Important installation information!
– Do not use the device in the open (only within closed rooms).
– Do not lay PHC bus line parallel to consumer and AC power lines..
– Pay attention to correct polarity of data cables (A, B).
– Do not conduct power supply (230V~ /50Hz) to PHC bus
(input connector 24V, +A, -B, 0V)!
– Switch off power supply before connecting or disconnecting bus line.
– Do not set the same module addresses for input pushbuttons.
– Before setting the module address, the PHC module needs to be
switched off and it must be secured against electrical discharge.
commissioning
• Carry out installation and switch on electrical system.
• Carry out PHC programming with PHC software.
• Carry out program transfer with PHC software.
T5
T6
T7
T8
status LeDs with
feedback signal
T3
T4
status LeDs with
feedback signal
T2
status LeDs with
feedback signal
GB - 1
D - 1

Werbung

loading

Diese Anleitung auch für:

Phc 4Phc 8