The CTI 140.DIO8 devices communicate with the com.tom POR-
TAL via Ethernet. The communication mechanism has a low data
volume and can be integrated easily in existing network infrastruc-
tures.
The device may be put into service and
operated by qualified personnel only.
The device is designed for an installation on a
grounded 35 mm DIN rail in dry rooms.
The power supply of the device must be a
grounded circuit PELV (connection between
functional earth and ground). The power
supply must be a limited power source ac-
cording to the EN60950-1 chap. 2.5 or must
be provided with an anti-surge fuse of 2 A.
The digital I/Os must be provided with a
detached anti-surge fuse of 4A.
Pin Assignment
Power Supplies
PIN
Description
FE
Functional earth
GND
Ground
VCC
24 VDC
Serial Interface (COM)
Pin
RS232
Pin 1
GND
Pin 2
CTS
Pin 3
-
Pin 4
Tx
Pin 5
-
Pin 6
RTS
Pin 7
-
Pin 8
Rx
CAN Interface
Pin
Description
Pin 1
CAN High
Pin 2
TERM
Pin 3
CAN Low
Pin 4
TERM
Ethernet Interface
Green LED
Link indication
Yellow LED
Activity indication
RS485
GND
-
B (+/Z)
-
A (-/Y)
-
TERM_B
-
Digital I/Os
Signal
Description
+
24 VDC
I 0
Digital input 0
I 1
Digital input 1
I 2
Digital input 2
I 3
Digital input 3
Q 0
Digital output 0
Q 1
Digital output 1
Q 2
Digital output 2
Q 3
Digital output 3
-
Ground
Status LEDs
PLC
PLC status
Portal
Portal status
LED 3
Freely programmable
LED 4
Freely programmable
Power
Device is powered
Other Interfaces
SD card interface
microSD card
USB interface
Micro USB (OTG Host & Slave)
Getting Started
Wire the com.tom device according to the technical data. Get
the
appropriate
Getting
http://www.com-tom.de/start and follow the steps described
there to put your device into operation. When using the GPJ
power supply connector (labeled in white), only a com.tom
GRAPHIC device may be connected to Port ETH1.3/GPJ.
Part Numbers
00571181 (WEB-PLC)
CTI 140.DIO8.W
00571265 (CODESYS)
CTI 140.DIO8.C
General Data
Size (W x L x H)
65 x 103 x 63 mm
Operating temperature
0 bis 55 °C
Electrical shock
Class III
Protection rating
IP20
EMC emission
IEC 61000-6-3
EMC immunity
IEC 61000-6-2
Compliance
CE, RoHS
Electrical Data
Supply voltage
24 VDC (15 %)
Active current
< 0.10 A (without I/Os)
≤ 0.5 A / output
Scope of supply
1 Piece
CTI 140.DIO8
1 Piece
microSD card
1 Piece
Start-up guide
2 Pieces
Connector 3-pin
1 Piece
Connector 8-pin
1 Piece
Connector 4-pin
1 Piece
Connector 10-pin
1 Piece
Label MAC-ID
documentation
at
Started
Copyright © 2018 Beck IPC GmbH
http://www.com-tom.de

Werbung

loading

Inhaltszusammenfassung für Beck com.tom INDUSTRY 140.DIO8

  • Seite 1 CAN High 1 Piece Connector 4-pin Pin 2 TERM 1 Piece Connector 10-pin Pin 3 CAN Low 1 Piece Label MAC-ID Pin 4 TERM Ethernet Interface Green LED Link indication Yellow LED Activity indication Copyright © 2018 Beck IPC GmbH http://www.com-tom.de...
  • Seite 2 com.tom INDUSTRY 140.DIO8 Inbetriebnahmeanleitung Die Kommunikation der CTI 140.DIO8-Geräte mit dem com.tom Digitale E/As PORTAL erfolgt via Ethernet. Der Kommunikationsmechanismus Signal Beschreibung hat ein geringes Datenaufkommen und lässt sich problemlos in 24 VDC vorhandene Netzwerkinfrastrukturen integrieren. Digitaler Eingang 0 Digitaler Eingang 1 Montage und Inbetriebnahme darf nur durch qualifiziertes Personal erfolgen.

Diese Anleitung auch für:

Cti 140.dio8