com.tom
INDUSTRY 100
Start-up Guide
The CTI 100 devices communicate with the com.tom PORTAL via
Ethernet and the existing network infrastructure. The communica-
tion mechanism has a low data volume and can be integrated easily
in existing network infrastructures.
The device may be put into service and
operated by qualified personnel only.
The device is designed for an installation on a
grounded 35 mm DIN rail in dry rooms.
The power supply of the device must be a
grounded circuit PELV (connection between
functional earth and ground). The power
supply must be a limited power source ac-
cording to the EN60950-1 chap. 2.5 or must
be provided with an anti-surge fuse of 2 A.
Pin Assignment
Power Supply
PIN
Description
FE
Functional earth
GND
Ground
VCC
24 VDC
Serial Interface (COM)
Pin
RS232
Pin 1
COM_GND
Pin 2
CTS
Pin 3
-
Pin 4
Tx
Pin 5
-
Pin 6
RTS
Pin 7
-
Pin 8
Rx
CAN Interface
Pin
Description
Pin 1
CAN High
Pin 2
TERM
Pin 3
CAN Low
Pin 4
CAN_GND
Ethernet Interface
Yellow LED
Link indication
Green LED
Activity indication
RS485
COM_GND
-
B (+/Z)
-
A (-/Y)
-
TERM_B
-
Status LEDs
PLC
PLC status
Portal
Portal status
LED 3
Freely programmable
LED 4
Freely programmable
Power
Device is powered
Other Interfaces
SD card interface
microSD card
USB interface
Micro USB (OTG Host & Slave)
Getting Started
Wire the com.tom device according to the technical data. Get
the
appropriate
Getting
http://www.com-tom.de/start and follow the steps described
there to put your device into operation.
Part Numbers
00571144 (WEB-PLC)
CTI 100.W
00571237 (CODESYS)
CTI 100.C
General Data
Size (W x L x H)
46 x 103 x 63 mm
Operating temperature
0 bis 55 °C
Electrical shock
Class III
Protection rating
IP20
EMC emission
IEC 61000-6-3
EMC immunity
IEC 61000-6-2
Compliance
CE, RoHS
Electrical Data
Supply voltage
24 VDC (15 %)
Active current
< 100 mA
Scope of supply
1 Piece
CTI 100
1 Piece
microSD card
1 Piece
Start-up guide
1 Piece
Connector 3-pin
1 Piece
Connector 8-pin
1 Piece
Connector 4-pin
1 Piece
Label MAC-ID
documentation
at
Started
Copyright © 2018 Beck IPC GmbH
http://www.com-tom.de

Werbung

loading

Inhaltszusammenfassung für Beck com.tom INDUSTRY 100

  • Seite 1 1 Piece microSD card Ethernet Interface 1 Piece Start-up guide Yellow LED Link indication 1 Piece Connector 3-pin Green LED Activity indication 1 Piece Connector 8-pin 1 Piece Connector 4-pin 1 Piece Label MAC-ID Copyright © 2018 Beck IPC GmbH http://www.com-tom.de...
  • Seite 2 Status-LEDs PLC-Status Portal Portal-Status com.tom INDUSTRY 100 LED 3 Frei programmierbar LED 4 Frei programmierbar Inbetriebnahmeanleitung Power Versorgungsspannung vorhanden Die Kommunikation der CTI 100-Geräte mit dem com.tom PORTAL erfolgt via Ethernet und der vorhandenen Netzwerkinfrastruktur. Der Weitere Schnittstellen Kommunikationsmechanismus hat ein geringes Datenaufkommen SD-Kartenschacht microSD-Karte und lässt sich problemlos in vorhandene Netzwerkinfrastrukturen...

Diese Anleitung auch für:

Cti 100