Beck com.tom INDUSTRY 100.UMTS.WLAN Inbetriebnahmeanleitung

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

com.tom
INDUSTRY 100.UMTS.WLAN
Start-up Guide
The CTI 100.UMTS.WLAN devices communicate with the com.tom
PORTAL via UMTS modem, Wi-Fi or Ethernet. The communication
mechanism has a low data volume and can be integrated easily in
existing network infrastructures.
The device may be put into service and
operated by qualified personnel only.
The device is designed for an installation on a
grounded 35 mm DIN rail in dry rooms.
The power supply of the device must be a
grounded circuit PELV (connection between
functional earth and ground). The power
supply must be a limited power source ac-
cording to the EN60950-1 chap. 2.5 or must
be provided with an anti-surge fuse of 2 A.
 UMTS modem
 Wi-Fi
Insert the SIM card in the device's rear before the installation on the
DIN rail. The device must be deactivated through this process.
Never use the device in areas where the operation of wireless
equipment is prohibited. You have to ensure that the maximum
permissible emission values are observed when selecting the an-
tennas place of installation (minimum distance of 20 cm to persons
and other antennas).The adherence of the protection against the
lightning norm VDE V 0185 is mandatory when installing the anten-
nas outside. The E.M.C lightning zone concept must be considered.
The device must be deactivated while working with the antennas.
Pin Assignment
Power Supply
PIN
Description
FE
Functional earth
GND
Ground
VCC
24 VDC
Serial Interface (COM)
Pin
RS232
Pin 1
GND
Pin 2
CTS
Pin 3
-
Pin 4
Tx
Pin 5
-
Pin 6
RTS
Pin 7
-
Pin 8
Rx
RS485
GND
-
B (+/Z)
-
A (-/Y)
-
TERM_B
-
CAN Interface
Pin
Description
Pin 1
CAN High
Pin 2
TERM
Pin 3
CAN Low
Pin 4
TERM
Ethernet Interface
Green LED
Link indication
Yellow LED
Activity indication
Status LEDs
PLC
PLC status
Portal
Portal status
GSM
Modem status
WiFi
Wi-Fi status
Power
Device is powered
Other Interfaces
SD card interface
microSD card
USB interface
Micro USB (OTG Host & Slave)
SIM card interface
Mini SIM (2FF)
Antenna interfaces
SMA connector (female)
Top: UMTS modem
Bottom: Wi-Fi
Getting Started
Wire the com.tom device according to the technical data. Get
the
appropriate
Getting
http://www.com-tom.de/start and follow the steps described
there to put your device into operation.
Part Numbers
00571217 (WEB-PLC)
CTI 100.UMTS.WLAN.W
00571308 (CODESYS)
CTI 100.UMTS.WLAN.C
General Data
Size (W x L x H)
46 x 103 x 63 mm
Operating temperature
0 bis 55 °C
Electrical shock
Class III
Protection rating
IP20
EMC emission
IEC 61000-6-3
EMC immunity
IEC 61000-6-2
Compliance
CE, RoHS
Electrical Data
Supply voltage
24 VDC (15 %)
Active current
< 180 mA
Scope of supply
1 Piece
CTI 100.UMTS.WLAN
1 Piece
Start-up guide
1 Piece
Connector 3-pin
1 Piece
Connector 8-pin
1 Piece
Connector 4-pin
1 Piece
Label MAC-ID
documentation
at
Started
Copyright © 2018 Beck IPC GmbH
http://www.com-tom.de

Werbung

loading

Inhaltszusammenfassung für Beck com.tom INDUSTRY 100.UMTS.WLAN

  • Seite 1 1 Piece Start-up guide Pin 4 1 Piece Connector 3-pin Pin 5 A (-/Y) 1 Piece Connector 8-pin Pin 6 1 Piece Connector 4-pin Pin 7 TERM_B 1 Piece Label MAC-ID Pin 8 Copyright © 2018 Beck IPC GmbH http://www.com-tom.de...
  • Seite 2 com.tom INDUSTRY 100.UMTS.WLAN Inbetriebnahmeanleitung Die Kommunikation der CTI 100.UMTS.WLAN-Geräte mit dem CAN-Schnittstelle com.tom PORTAL erfolgt via Mobilfunkverbindung, WLAN oder Beschreibung Ethernet. Der Kommunikationsmechanismus hat ein geringes Da- Pin 1 CAN High tenaufkommen und lässt sich problemlos in vorhandene Netzwer- Pin 2 TERM kinfrastrukturen integrieren.

Diese Anleitung auch für:

Cti 100.umts.wlan