2402STE Intelligent Switch Mode Power Supply: EN54-4 Certified
27.6Vdc 2A PSU with Intelligent Battery Charging, Monitoring and Remote Fault Signalling
Overview
The 2402STE is a fully featured EN54-4 approved power supply ideal for use in Fire Systems and Access control applications. Its
regulated 27.6V dc output will supply up to 2A continuous into the load, in addition to providing up to 0.8A for charging the standby
batteries. The power supply output features electronic short circuit protection under both mains and standby battery operation.
Maximum battery life is assured through continuous active battery monitoring and the use of a three stage charger, comprising bulk,
absorb and temperature compensated final float phase depending upon battery condition. Deep discharge protection prevents
premature battery failure when operating from standby for extended periods. Two sets of volt free solid state relay fault output signal (i)
loss of mains and (ii) battery fault, charger fault and loss of output.
Certified by VdS to EN54-4:1997 +A1: 2002 + A2: 2006
2A current to load at 27.6V dc nominal regulated output
Electronic overload protection shuts down output until overload or short circuit is removed
Battery Monitor detects battery missing, low battery, short-circuit or reverse connection
Battery charging circuit is energised only when a battery is correctly connected and the battery voltage is greater than 14V
No loss of output during automatic connection of battery to load on loss of mains
Deep discharge protection disconnects battery from load when battery voltage falls to 21V
Automatic start-up on battery only
Fault indicator LED (Red) flashes on detection of output fault, battery fault, charger fault and mains failure
Mains indicator LED (green) showing mains present
Compliance
This power supply unit complies with the following European Directives:
Low Voltage 2006/95/EC
Specification
Input
Voltage
Frequency
Current
Inrush current
Mains input fuse
Output
Voltage
Load Current
Ripple
Load output fuse
Overload
Standby Battery
Battery Capacity
Battery fuse protection
Battery Charging
Low Battery Threshold Voltage
Deep discharge protection
Quiescent current - no load
Quiescent current - battery cut off
Mechanical
Case material
Size
Weight
Environmental
Temperature
Connections
O/P + and -
PSU Fault
EPS fault
Temp sensor
BATT + and -
FAN + and -
www.acornfiresecurity.com
EMC 2004/108/EC
WEEE 2002/96/EC
93Vac minimum, 264Vac maximum
45Hz – 65Hz
1.25A maximum for a 2A load and 0.8A battery charging
O
30A maximum @ 25
C, 110Vac for 10ms
T3.15A 20mm, 250Vac HBC
26.0Vdc – 28vdc on mains power / 18Vdc – 26Vdc on battery standby
0 - 2A
100mV max over full rated mains voltage
T2A 20mm, 250Vac glass
Electronic shutdown at 4.5A until overload or short circuit removed
2 x 17Ah maximum (e.g. Yuasa NP17-12) series connected
T2A 20mm glass
Constant current (0.8A) bulk charging to 80% within 24 hours, float charging to 100% within 48
hours
23V nominal
Battery disconnect at 21V nominal
25mA nominal
<70μA
1.2mm steel, white powder coated
400mm W x 420mm H x 80mm D
6.2kg (excluding batteries)
O
-10 to +40
C (operating) 95% RH non-condensing
O
-20 to +80
C (storage)
Voltage output to load
Solid State Relay output contacts
Solid State Relay output contacts
Connection to battery temperature sensor
Connections to standby batteries
No Connection
www.acornfiresecurity.com
VdS
G209142
RoHs 2002/95/EC
CPD 89/106/EC
09
0786-CPD-20787

Werbung

Inhaltsverzeichnis
loading

Inhaltszusammenfassung für Elmdene 2402STE

  • Seite 1 Overview The 2402STE is a fully featured EN54-4 approved power supply ideal for use in Fire Systems and Access control applications. Its regulated 27.6V dc output will supply up to 2A continuous into the load, in addition to providing up to 0.8A for charging the standby batteries.
  • Seite 2 www.acornfiresecurity.com Features Loss of Mains and Brown-out compensation If the mains input has been lost for greater than 10s, a Loss of Mains condition is detected, an EPS Fault is signalled and the green Mains LED is extinguished. Short duration mains “brown-out” conditions are not signalled thus reducing nuisance alarms. The red Fault LED will show a heart- beat pulse indicating that the PSU is operating correctly in standby mode.
  • Seite 3: Installation

    www.acornfiresecurity.com Installation This unit is only suitable for installation as permanently connected equipment. The PSU is NOT SUITABLE for external installation. This unit must be fed from a mains power source having a separate (approved) disconnect device and fitted with a fuse or other over-current protection device rated at 3A maximum.
  • Seite 4: Maintenance

    Dispose of used batteries according to the battery manufacturer’s instructions and all local and national regulations The packaging supplied with this product may be recycled. Please dispose of packaging accordingly. Specifications subject to change without notice. © 2013 Elmdene International Ltd www.acornfiresecurity.com...
  • Seite 5: Übereinstimmung Mit Richtlinien

    27,6V DC 2A Energieversorgungsgerät mit intelligenter Batterieladung, Überwachung und Störungsfernmeldung. Überblick Das 2402STE ist ein Energieversorgungsgerät mit sämtlichen EN54-4 - Leistungsmerkmalen, ideal geeignet für Brandmeldeanlagen und Zugangskontrollvorrichtungen. Sein geregelter Spannungsausgang von 27,6V DC kann gleichzeitig bis zu 2A zur fortlaufenden Versorgung der Last und bis zu 0,8A zur Ladung der Notstrombatterie liefern.
  • Seite 6 www.acornfiresecurity.com Anschlüsse O/P (Ausgang) + und - Spannungsausgang zur Last Störung bei Energieversorgungsgerät Festkörperrelais-Ausgangskontakte Störung bei EPS Festkörperrelais-Ausgangskontakte Temp.-Sensor Anschluss für Batterietemperatur-Sensor BATT + und - Anschlüsse für Notstrombatterien FAN + und - Keine Verbindungen Merkmale Kompensierung von Stromausfall und Spannungsabfall Wenn die Netzstromversorgung länger als 10 s ausfällt, wird eine Unterbrechung der Stromversorgung [Loss of Mains] festgestellt und eine EPS-Störung signalisiert.
  • Seite 7: Einbau

    www.acornfiresecurity.com Netzverbindung besteht. Batterie voll Normaler Betrieb Keine aufgeladen. Netzverbindung getrennt. Es liegt keine Überprüfen Sie, warum keine Notstrombetrieb Störung vor. Netzverbindung besteht Batterie-Antriebslast. Softwarefehler entdeckt. oder A Interne Störung Energieversorgungsgerät läuft im Zurück an Hersteller AUERHART sicheren Modus [Safe Mode]. Ausgangssicherung durchgebrannt Überprüfen und ersetzen Sie die AUERHAFTES...
  • Seite 8: Wartung

    Entsorgen Sie gebrauchte Batterien gemäß den Anleitungen des Herstellers und gemäß allen regionalen und nationalen Bestimmungen Die Verpackung dieses Produkts kann recycelt werden. Bitte entsorgen Sie die Verpackung ordnungsgemäß. Spezifikationen können ohne vorherige Mitteilung geändert werden. © 2011 Elmdene International Ltd www.acornfiresecurity.com...

Inhaltsverzeichnis