Menu
This takes you to the main menu
This takes you to the settings menu. You can
manage your phone numbers and SIM card PIN
here and set the language.
If you click on «Monitor» in the home screen,
all connected sensors will be displayed with
their status. We recommend this setting during
monitoring.
If you click on «Devices» in the home screen, you
will get to the menu to manage the individual
sensors.
More sensors can be ...
added: See the «Start-up» section.
deleted: To do this, click and hold down the
corresponding sensor. You will then be prompted
again to confirm the deletion.
renamed: To rename a sensor, briefly click on the
corresponding sensor name. The menu window for
renaming will open.
This shows whether an activated SIM card is inser-
ted and active.
Press to switch off the device.
28
Function
General
You can monitor up to 40 sensors with one display
module.
Outdoor use is not recommended. Otherwise false
alarms in humid weather or rain cannot be ruled out.
The sensor will react when the non-woven fabric on
the back of the sensor becomes moist. 1−2 drops of
liquid are sufficient to trigger an alarm. Transmission
takes place a maximum of 120 seconds after the
non-woven fabric is soaked through. The time it
takes the non-woven fabric to soak through depends
on the viscosity of the liquid.
The radio connection is checked at 30-minute
intervals. After two consecutive negative connection
checks, an alarm signal will be sent.
Alarm
There are 3 different status indicators on the display
module for each sensor.
Status indicators on the display module are:
Green:
Sensor active, connected, no leakage
Grey:
The connection between the sensor and the
display module is interrupted or the non-woven is not
inserted correctly
Red:
Alarm caused by leakage
EN