Konfigurationsbeispiel no. 3
Configuration example IIA - IIB and IIC application - F030-P-OT-PX-XI-ZB
TERMINAL CONNECTORS
F0-series
Supply backlight
Common ground
Common ground
Main supply
Common ground
Supply *
Signal
Common ground
*Sensor supply voltage for pulse type P: Terminal 3: 1.2V - 3.2V DC.
Please note: type PX may be used in combination with the battery (type PC). PX will power the unit; the battery will be disabled automatically till power is disconnected.
Konfigurationsbeispiel no. 4
Configuration example IIA - IIB and IIC application - F030-P-OT-PD-XI-ZB
TERMINAL CONNECTORS
F0-series
Supply backlight
Common ground
Common ground
Supply *
Main supply
Common ground
Supply *
Signal
Common ground
*Sensor supply voltage for pulse type P: Terminal 3: 1.2V - 3.2V DC. Terminal 6: 8.2V DC.
Please note: type PD may be used in combination with the battery (type PC). PD will power the unit; the battery will be disabled automatically till power is disconnected.
Backlight option: type ZB
Intrinsically Safe apparatus
Control output type OT: passive transistor
Power supply type PX: 8-30V DC
I.S. flowmeter
input type: P
pulse
Abb. 18: Konfigurationsbeispiel Eigensicherheit.
Backlight option: type ZB
Intrinsically Safe apparatus
Control output type OT: passive transistor
Power supply type PD: 16-30V DC
I.S. flowmeter
input type: P
pulse
Abb. 19: Konfigurationsbeispiel Eigensicherheit.
HF030PDE_v0402_03 Atex_IECEx_CSA_FM.doc
HAZARDOUS AREA
SAFE AREA
= max. 30 V
Uo
Io
= max. 200 mA
= max. 0,75 W
Po
= max. 30 V
Uo
= max. 200 mA
Io
= max. 1,2 W
Po
= max. 30 V
Uo
= max. 200 mA
Io
= max. 1,2 W
Po
Uo
= max. 30 V
= max. 150 mA
Io
= max. 0,92 W
Po
Note: above values are safety values.
Consult the technical specification for operational values.
HAZARDOUS AREA
SAFE AREA
Uo
= max. 30 V
= max. 200 mA
Io
= max. 0,75 W
Po
= max. 30 V
Uo
= max. 200 mA
Io
Po
= max. 1,2 W
= max. 30 V
Uo
= max. 200 mA
Io
= max. 1,2 W
Po
Note: above values are safety values.
Consult the technical specification for operational values.
Power supply
For example
MTL5025
Power supply or
switch interface
For example
MTL5025
MTL5011B
e.g. relay
Power supply
For example
MTL5025
Power supply
For example
MTL5025
Power supply
For example
MTL5025
Power supply or
switch interface
For example
MTL5025
MTL5011B
e.g. relay
Power supply
For example
MTL5025