About the control
Here you can view information on
software versions.

INSTALLATION

OJ-AIR2-HMI-35T can be installed in two ways: either in a wall
box/panel front or directly on a flat surface.
Installation on flat surface
The back cover of the HMI is equipped with a keyhole-shaped
opening which can be used to hang the unit on a flat surface
(see Fig. 1). Use a screw that is max. 3.5 mm in diameter with a
head no larger than 9 mm.
Installation in wall box/panel front
If OJ-AIR2-HMI-35T is to be installed in a wall box or panel front,
the back cover must be removed. Firstly, the front cover must be
detached by gently releasing the catch on the bottom of the unit
with a flat screwdriver and then tipping the cover outwards
(see Fig. 2).
Once the front cover has been detached, the two screws holding
the back cover in place can be removed (see fig. 3).
The back cover can now be detached and the front cover refitted.
The baseplate is equipped with several screw holes. The dimen-
sioned drawing (see fig. 4) can be used as a drilling template.
The baseplate should be secured with at least two screws tight-
ened to a torque of max. 0.8 Nm.
Installation depth is 20 mm.