Product description
The USB RF interface UIMrf connects a PC to KNX RF via RF data
connection. With the ETS it works as programming interface. No specific
USB driver is required.
As KNX RF Ready S-mode device (RF1.R) UIMrf provides access to
KNX RF devices and E-mode installations for:
Commissioning
Addressing
Configuring
The protocol used for communication between interface and host is the
flexible "cEMI" protocol. The connection between KNX and a PC is
handled by the Falcon driver. UIMrf supports extended frames and long
messages with up to 208 byte APDU length. Easy software handling
also under operating systems not supported by the Falcon driver (e.g.:
Linux) is ensured. For specific diagnostic applications like EITT the UIMrf
supports the "Raw Frame" operating mode. UIMrf is conforming to KNX-
AN168.
Technical specifications
Power input
Power supply:
Current consumption:
Housing
Dimensions (HxWxD):
KNX RF connection:
USB connector:
Weight:
Environmental conditions
Operating temperature:
Storage temperature:
Ambient humidity:
Electrical safety
Pollution degree (IEC60664):
Protection type (IEC60529):
Protection class (IEC61140):
Overvoltage category (IEC60664):
Approbation (ISO/IEC14543-3):
Mounting, commissioning and safety notes
 After connection to USB, the device works with its default settings as
intended
 For planning and construction of electric installations the appropriate
specifications, guidelines and regulations in force of the respective
country have to be complied
 Installation only in dry locations
 For changing the configuration use the ETS
Requirements of Directives RED and RoHS are met. Standards for
residential, commercial, and industrial environments are fulfilled.
Hereby, TAPKO Technologies GmbH declares that the radio equipment
type UIMrf is in compliance with Directive 2014/53/EU.
The full text of the EU declaration of conformity is available at the
following internet address:
www.tapko.de/ce
Release version/date: R1.0 / December 2018
© 2001-2018 TAPKO Technologies GmbH
Im Gewerbepark A15, 93059 Regensburg, Germany
Details, modifications and corrections may be subject to change without notice. TAPKO gives no warranty for the accuracy of the document. All rights reserved.
Operating Instructions
Visualization
Protocol
Diagnostic operations
USB, 5 V DC
Tx < 25 mA, Rx < 5 mA
8.7 x 71 x 23 mm
RF antenna, integrated
USB2.0 (Type A, male)
10 g
-10...55 °C
-20...60 °C
5...93 % (non-condensing)
2
IP20
III
III
KNX-certified
Connectors, buttons and LEDs description
A
USB connector
RF data
Frequency range:
Tx transmit power:
RF range:
CE Marking
EU Directives:
Standards:
Installation and maintenance
 The housing must not be opened
 Protect the device from moisture, dirt and damage
 The device needs no maintenance
 If necessary, the device can be cleaned with a dry cloth
 In the case of damage (at storage, transport) no repairs may be
carried out by unauthorized personnel
 Configuration details and ETS database:
UIMrf
B
RF antenna
868.3 MHz ± 300 kHz
+ 3.7 dBm
100 m
RED
(2014/53/EU)
RoHS
(2011/65/EU)
ETSI EN300220-1
ETSI EN300220-2
EN301489-1
EN301489-3
EN50491-5-2
EN50581
EN61000-6-2
EN61000-6-3
EN62368-1
EN62479
www.tapko.de/uimrf

Werbung

loading

Inhaltszusammenfassung für TAPKO UIMrf

  • Seite 1 Release version/date: R1.0 / December 2018 © 2001-2018 TAPKO Technologies GmbH Im Gewerbepark A15, 93059 Regensburg, Germany Details, modifications and corrections may be subject to change without notice. TAPKO gives no warranty for the accuracy of the document. All rights reserved.
  • Seite 2 Internetadresse verfügbar: www.tapko.de/ce Version/Veröffentlichung: R1.0 / Dezember 2018 © 2001-2018 TAPKO Technologies GmbH Im Gewerbepark A15, 93059 Regensburg, Germany Hier enthaltene Daten können sich ohne vorherige Ankündigung ändern. TAPKO garantiert nicht die Richtigkeit und Vollständigkeit des Dokuments. Alle Rechte vorbehalten.