WARNING! WEAR GOGGLES AND GLOVES
CAUTION: When removing the cylinder, make sure the hex scale adapter does not unthread from the scale.
CAUTION: Avoid leaving liquid refrigerant in tube. Liquid in the tube and an increase in temperature could cause
the pressure to increase high enough to cause damage to the tube and scale. The check valve in the 1/4" flare
fitting on the scale platform allows the cylinder to be removed to draw any liquid in the tube into the system.
1. Open the battery cover and insert 3 AAA batteries according to the polarity indicated in the battery compartment.
2. Press the ON/OFF/TARE key. The display will show "88888" and transition to "0"
3. Connect the brass hex cylinder scale adapter to the scale. Hold scale tray by
hand while tightening. Be sure it is tight and secure.
NOTE: Do not over tighten.
4. Attach the refrigerant cylinder to the brass hex cylinder scale adapter, please
make sure the threads fit properly without any cross threading. With the valve
on the hose closed, hold the cylinder so the cylinder fitting is up and hold the
scale upside down. Turn the cylinder into the scale fitting. This way, the small
amount of refrigerant that leaks out while tightening will be vapor. Refrigerant
will begin to flow through the scale into the tube.
5. FIRST TIME USE: Partially open the valve, at the end of the nylon tube to purge
the air. Once the refrigerant starts to flow, close the valve immediately.
NOTE: Should you decide to use different refrigerant you must purge the current refrigerant from the hose and repeat
the above steps with the new refrigerant.
TARE WEIGHING
This scale is designed with a TARE WEIGHING function. Press the ON/OFF/TARE key, the display will transition to "0."
Connect the valve to the system and open the valve to charge. The scale will start displaying the weight of the material
being removed from the cylinder. When a sufficient amount of charge is reached, close the valve and disconnect it from
the system. NOTE: You may leave the cylinder on the scale or disconnect it from the scale.
UNIT CHANGE
You can change the weight unit by pressing the UNIT key.
POWER OFF
When you finish the operation, you can turn off the scale by pressing and holding the ON/OFF/TARE key. This scale is
designed with an auto-off function to save the battery power. It automatically turns off its power if the scale is not used
within 3 hours.
BATTERY REPLACEMENT
If "
" message appears in the display when attempting to weigh, replace the scale's 3 AAA
batteries according to the polarity indicated in the battery compartment.
CALIBRATING THE DEVICE
1. In power off mode, press the UNIT and ON/OFF/TARE key simultaneously to turn the scale on, when a count value is
seen, release the two keys.
2. Press the ON/OFF/TARE key, LCD will show "ZERO" then calibration weight 5000 g.
3. Place a 5 kg weight on the platform, press the ON/OFF/TARE key, the LCD will show "CAL" then "PASS", calibration is
completed.
NOTE: Mastercool recommends using a certified 5 kg weight for the best accuracy.
4. After calibration is complete, the scale will go back to weighing mode, the LCD will show the weight on the platform.
2
HIGH PRECISION CHARGING SCALE INSTRUCTIONS
www.mastercool.com
English
SCALE TRAY
HOLD HERE TO TIGHTEN HEX ADAPTER
g
ON/OFF
UNIT
TARE
oz
CAPACITY: 5000 g x 1 g / 176 oz x 0.1 oz