Safety Guidelines

1.
Follow the installation instructions.
2.
Use the appliance
• according to its intended use
• in good condition
• with due regard to safety and risk of danger.
3.
Note that the appliance is exclusively for use in the
applications detailed in these installation instructions
(see 2 Technical Data). Any other use will not be
considered to comply with requirements and would
invalidate the warranty.
4.
Please take note that any assembly, commissioning,
servicing and adjustment work may only be carried
out by authorized persons.
5.
Immediately rectify any malfunctions which may
influence safety.
2

Technical Data

Media
Medium:
Connections/Sizes
Connection size:
Pressure values
Max. inlet pressure:
Opening pressure:
Min. inlet pressure:
Operating temperatures
Max. operating temperature
medium:
Specifications
Installation position:
3

Options

For Options visit homecomfort.resideo.com/europe
4

Assembly

It is necessary during installation to comply with local
requirements, to follow codes of good practice and to follow
the installation instructions.
The installation location should be protected against frost and
be easily accessible
4.1 Installation Guidelines
Install shut-off valves
Install in horizontal pipework with spring bonnet
directed upwards
Ensure good access
Cold drinking water
DN65 - DN200
10 bar
DN65 - DN100:
0.5, 1 or 1.5 bar as required
DN125 - DN200:
0.5, 1 bar as required
Opening pressure + 1 bar
40 °C
Horizontal with spring bonnet
upwards
GB
– Pressure gauge can be read off easily
– Simplifies maintenance and inspection
Mechanical disconnectors must not be fitted in any
areas or ducts where poisonous gases or vapours
may be present or where flooding can occur
In order to avoid flooding, it is recommended to
arrange a permanent, professionally dimensioned
wastewater connection
These armatures need to be maintained regularly
4.2 Assembly instructions
Flush connecting pipework thoroughly before
installation
Install the backflow preventer with good accessibility
and with flow in the correct direction
Install the backflow preventer only in horizontal
pipework and with the discharge tundish 
downwards
A clearance of A
backflow preventer for maintenance purposes
DN
65
80
Amin 170
200
It is recommended that a Y-strainer  (e.g. FY 69) be
fitted upstream to protect the backflow preventer
against coarse dirt
Fit shut-off valves  and  either side of the
backflow preventer
Install a small drain cock  upstream of the backflow
preventer
Connect discharge pipe to discharge tundish 
4.3 Commissioning
As supplied the hydraulically actuated changeover valve is
closed and the backflow preventer is in the shutoff position.
Commissioning should be in the following sequence:
1.
Slowly open shut-off valve 
When reaching the minimum inlet pressure the
backflow preventer turns to flow position so that the
complete pipe unit is filled up to the shut-off valve 
2.
Slowly open shut-off valve  . Fill and vent the
system
3.
When the system has been filled, the backflow
preventer is ready for use (the backflow preventer is
then in the flow position).
Backflow preventers of this type are normally in the flow
position. Shut-off occurs only when the supply pressure falls
below the operating pressure of the pipe separator.
The operating position is indicated on the spring bonnet  .
Shut-off position: Green spring bonnet  is visible.
The backflow preventer has shut-off
Flow position: Green spring bonnet  is not visible
4
must be provided above the
min
100
125
150
240
270
320
MU1H-1211GE23 R0320
200
440