ENGLISH
BL-210-00-868 UP ENOCEAN REPEATER
Part Nr.: 10986
Assembly instructions and operating manual
Subject to change without prior notice.
Last change: 13.04.2020
www.deuta-controls.net
Standards
CE compliance:
2014/53/EU RED Directive
2011/65/EU RoHS Directive
Product safety:
DIN EN 60950-1:2011 + A12 Cor. 1:2012
+ Cor. 1:2012
EMC/EMI:
EN 61000-6-2:2005
EN 61000-6-3:2007 + A1:2011 + Cor 1:2012
EN 301 489-1:2011 V1.9.2
EN 301 489-3:2013 V1.6.1
EN 300 220-2:2012 V2.4.1
Technical data
Supply voltage:
230 V AC / 50 Hz
Power consumption: Typ. 1.4 W, max. 1.5 W
Input:
Pot. free contact, normally open, terminals 1+2
Transmit-/
receive center frequency:
Occupied frequency band:
Maximum transmission power:
EN 300 220 receiver category:
Connectors:
Screw terminals, max. 1.5 mm
1.0 mm
Housing material:
UL-V0, black
Protection class:
IP20 / indoor use only
Operating temp.:
+5 to +50 °C
Storage temp.:
+5 to +50 °C
Weight:
40 g
Safety instructions
Warning: Electrical equipment may only be installed by electrically
skilled persons. The device must not be opened. All relevant interfaces
are accessibly from the outside.
The device must not be used in applications related to life-sustaining
measures or where any human being, animal or material asset might
be menaced.
DEUTA Controls GmbH
Paffrather Straße 140
51465 Bergisch Gladbach
Tel: +49 (0) 22 02 285 57 – 60
Fax: +49 (0) 22 02 285 57 – 79
E-Mail: info@deuta-controls.de
868.3 MHz / ASK (EnOcean)
868.0 - 868.6 MHz
typ. 3 dBm @ 868.300 MHz
2
inflexible, max.
2
flexible with cable end sleeves
2
Summary
The EnOcean-Repeater BL-210-00-868 UP ENOCEAN REPEATER provides the
following interfaces:
• 1x bi-directional EnOcean-Master (868 MHz)
• 1x Service button (in the housing, left side)
• 1x Service LED red (in the front)
• 1x 230 V AC power supply
The BL-210 EnOcean-Repeater provides an EnOcean wireless
transceiver, and acts as a level 1 or level 2 EnOcean repeater to
increase the possible maximum operating distance between
EnOcean sensors, EnOcean actors and control systems with EnOcean
interface.
The device is powered directly by 230 V AC. The Repeater mode
(level 1 or level 2) is selected by pushing the service button.
Scope of this operating manual / assembly instruction:
BL-210-00-868 UP ENOCEAN REPEATER, part nr. 10986
Page 1
Electrical connections
The BL-210 has to be supplied by 230 V AC line voltage. For details refer
to the technical data as specified in this document. The maximum cable
cross-section is 1,5 mm
conductors.
Connection plan
Installation/ safety precautions
• The BL-210 is prepared for the installation in a flush-mounting box /
in –wall mounting
• No external 868 MHz antenna is necessary.
• There must be an easily accessible electrical separator to disconnect
the power supply from the BL-210.
• There must be an over-current protection device in series with the
BL-210 power supply (10A).
• Once the BL-210 is mounted, the user must not have direct access to
the power supply connectors (230 V AC).
• BL-210 is not suitable to be used in IT networks (without a neutral
conductor).
• The product label of the BL-210 must be visible after the installation.
• Mounting of the BL-210 has to be done while power is switched off.