Heatalarm

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Commercial reference: 3003-001
Developed by CAVIUS
PLEASE
READ THE USER GUIDE
CAREFULLY BEFORE USE AND
RETAIN FOR FUTURE USE!
This Thermal Heat Alarm is designed for areas not suitable
for smoke alarms due to high risk of false alarms such
as; kitchens, garages or workshops.
Technical information:
Type of alarm:
heat alarm detects
CAVIUS
1) rapidly increased temperature level
2) absolute heat level of 58 degrees C.
Sound output: The minimum sound level is 85dB at 3
meter.
Battery: Powered by a non-replaceable 3v CR123A Lithium
battery with 10-year life (included).
Low battery indicator: A short acoustic "beep" will
sound and the LED will flash every 48 seconds when
the battery is near the end of its life. In this stage it will
continue for minimum 30 days.
The heat alarm is not active unless it is inserted in the
mounting base.
The best areas to mount the alarm:
• Areas not suitable for smoke alarms due to high
risk of false alarms
• Kitchen area
• Bathroom
• Garage or workshop
Additional alarms increase the security.
Minimum smoke alarms
Minimum heat alarms
The alarm may NOT be placed:
• In rooms where the temperature goes outside
-10ºC to +50ºC.
• Bedrooms
• Lounge
• Dining room
• Hallway
• Family room
NOTE: In areas where smoldering fires occur over flaming
fires, photoelectric smoke alarms are still the best to be in-
stalled.
UK
Placement:
The heat alarm is design to be installed on a ceiling or
wall. Never install directly above the oven/hob/stove.
Ceiling
Wall
Minimum 30cm and
maximum 50cm from
ceiling
Ceiling
Installation of alarm:
Info: The label in the product must not be removed due to
important information regarding the product.
1. The heat alarm is not in the mounting base when pur-
chased. Use the mounting base ring to mark the screw
holes on the ceiling. Use the enclosed screws and plugs
for installing the mounting base.
Test/Hush button
Alarm audible alert
Mounting base
Ceiling
Wall
Minimum 50cm
from wall
Minimum 30cm
and maximum 50cm
from stove
Peak ceiling
Mark up screw holes with a pen
Use the enclosed screws and
plugs for installation
2. Mount the heat alarm to the base
by using the smart clip-on-ceiling
mechanism. After mounting, test the
heat alarm by pressing the test but-
ton and get an alarm signal.
Heat alarm signal: The heat alarm
has a visual and acoustic signal. In the passive state,
the LED will flash every 48 seconds to indicate normal
function. In alarm state the LED will speed up flash,
and the alarm will emit a sweeping sound pattern
design to alert occupants.
Hush function: In case of unintentional or false alarms,
push button for 2 seconds.This will mute the alarm for
10 minutes, after which time the alarm will automatically
resume its normal function.
Maintenance: Test the heat alarm at least once per
quarter, by pushing the test button. The heat alarm
should give a loud alarm tone.
Fault finding: If the heat alarm activates without visible
cause, then possible cause could be:
You may have your heat alarm too close to the cooking
hobs and stove. Try reinstalling slightly further away to
alleviate any issues.
If the heat alarm does not work, when the test button is
pushed, the probably cause is a faulty battery, and the
heat alarm must be replaced.
Other information: Do not paint the heat alarm.
Disposal: For product, please dispose properly at end
of life. This is electronic waste that should be recycled.
The CE mark affixed to this product confirms its compliance
with the European Directives which apply to the product.
Tested to comply to the standard of system heat alarms
EN54-5 class A1/R.
Alarm condition aural signal pattern according to ISO 8201.
All Rights reserved: CAVIUS Aps assumes no responsibility
for any errors, which may ap pear in this manual. Further-
more, CAVIUS Aps reserves the right to alter the hardware,
software, and/or specifications detailed herein at any time
without notice, and CAVIUS Aps does not make any com-
mitment to update the information contained herein. All the
trademarks listed herein are owned by their respective owners.
Copyright © CAVIUS Aps.
Developed by CAVIUS Aps
Julsøvej 16, DK-8600
Manufactured in P.R.C.
127617 rev2

Werbung

loading

Inhaltszusammenfassung für Cavius 3003-001

  • Seite 1 All Rights reserved: CAVIUS Aps assumes no responsibility for any errors, which may ap pear in this manual. Further- • Bedrooms more, CAVIUS Aps reserves the right to alter the hardware, • Lounge software, and/or specifications detailed herein at any time Installation of alarm: •...
  • Seite 2 Schraubenlöcher mit einem Stift markieren H I T Z E Akustisches Verwenden Sie zur Installation M E L D E R Alarmsignal die mitgelieferten Schrauben und Dübel Artikelnummer: Cavius 3003-001 Eine Entwicklung von CAVIUS LESEN SIE DIE BEDIENUNG- Montagesockel SANLEITUNG BITTE GEBRAUCH SORGFÄLTIG...