Code for voltage and No. of poles
acc. to UL
Voltage
2-pole + PE
125V 60Hz
250V 60Hz
480V 60Hz
3-pole + PE
600V 60Hz
480V 60Hz
250V 40Hz
125/250V 60Hz
3-pole + N + PE
600V 60Hz
277V 60Hz
120/208V 60Hz
Dimensions in mm
X = fixing dimensions
Wall socket,
4- and 5-pole
Plug, 4- and 5-pole
2 2 2 2 2
Cooper Crouse-Hinds GmbH
Downloaded from
www.Manualslib.com
Annex to operating instructions
Plug and socket system 60A, GHG 514
1 1 1 1 1
T T T T T echnical data
echnical data
echnical data
echnical data
echnical data
1.1
1.1
1.1
1.1
1.1
Plug and socket GHG 514
Plug and socket GHG 514
Plug and socket GHG 514
Plug and socket GHG 514
Plug and socket GHG 514
Explosion category:
for USL
for CNL
Certifications and Compliances:
for CNL
Rated voltage:
Rated current:
Back-up fuse:
without thermal protection
Clock
with thermal protection
Colour face
Switching capacity:
(PE)
Perm. ambient temperature:
yellow
4 h
Special versions permit deviating temperatures.
blue
6 h
Perm. storage temperature in original packing:
red
7 h
Protection category acc. to IEC 60529
with closed and secured hinged cover as well
as combinations properly plugged together
black
5 h
Insulation class acc. to IEC 61140:
red
7 h
Cable entry:
blue
9 h
Wall socket
orange 12 h
plug / Coupler
Supply terminal:
Wall socket
black
5 h
red
7 h
Plug
blue
9 h
Test torques:
Cover screws
Terminals, plug
Terminals, wall socket
Self-cutting screws size 4
Self-cutting screws size 5
Self-cutting screws size 8
Weight:
wall socket
plug
wall socket
plug
Auxiliary contact:
Rated voltage:
Rated current:
Switching capacity:
GHG 514, 4-pole 50/60Hz
w/o auxiliary contact
contact
manuals search engine
4-pole
GHG 514 44
4-pole
GHG 514 74
5-pole
GHG 514 45
5-pole
GHG 514 75
Contact arrangement
with auxiliary
AEx de II C T6
Ex de II C T6
Class I, Zone 1
Class I, Division 2 -
Groups A, B, C and D
Class II, Division 1 -
Groups F and G
up to 600 V, 60 Hz
max. 60 A
max. 60 A
max. 80A gL
690V / 80A
-20° C to + 40° C (catalogue version)
-55° C to + 80° C
IP 66 (catalogue version)
I - is complied with by the devices
(catalogue version)
2 x M40, (1 x hub M40/1/4" NPT, 1 x blanking plug)
Ø 26 - 34 mm
Cross section
Stripped wire length
2 x AWG 11 - 4
19 mm
(with cable lugs 1 x AWG 2)
1 x AWG 11 - 5
12 mm
(with cable lugs 1 x AWG 4)
2.5 Nm
2.4 Nm
3.5 Nm
2.0 Nm
3.0 Nm
3.5 Nm
(catalogue version)
approx. 8.10 kg
approx. 0.75 kg
approx. 8.15 kg
approx. 0.80 kg
690V VAC
20A
AC 15
400V / 6A
DC 13
24V / 2A
GHG 514, 5-pole 50/60Hz
w/o auxiliary contact
with auxiliary
contact

Werbung