8 Display shows PMd / tIME / 0005 (or the last loaded value)
9 Act on
UP/DOWN
Delay time can be selected on fixed steps: 5 / 8 / 10 / 15 / 20 / 30 / 60
minutes
10 Press
ENTER
11 Display shows PMd / tYPE / ACt (or the last loaded value)
12 Act on
UP/DOWN
ACt
active power
rEA
reactive power
APP
apparent power
13 Press
ENTER
14 Display shows rES / PMd / no
15 If you don't want to reset average power counting, press
to item 16
If you want to reset average power counting, act on
display: rES / PMd / YES and then press ENTER.
16 Display shows rES / hoUr / no
17 If you don't want to reset run hour meter counting, press ENTER and pass
to item 18
If you want to reset run hour meter counting, act on
display: rES / hoUr / YES and then press ENTER.
18 Display shows PASS / 0000
19 Press
UP
to load the access key (usually 2001)
20 Press
ENTER
21 Display shows tA / 0001 0001 (or the last loaded value)
22 Act on
UP/DOWN
max.9999 (ex. 800/5A = ratio 160)
For direct connection, i.e. without external current transformer, it is neces-
sary to load a transformer ratio equal to 1
23 Press
ENTER
24 Display shows tV / 0001.0 (or the last loaded value)
25 Act on
UP/DOWN
max10,0 (ex. 600/100V = ratio 6,0).
For direct connection, i.e. without external VT, it is necessary to load a
transformer ratio equal to 1,0.
keys to load the average power delay time
keys to load the quantity related to the average power:
keys to load the external C.T. transformer ratio
keys to load the external V.T. transformer ratio
ENTER
and pass
UP/DOWN
until you
UP/DOWN
until you