Herunterladen Inhalt Inhalt Diese Seite drucken

Hitachi ATW-MBS-02 Installations- Und Betriebshandbuch Seite 17

Vorschau ausblenden Andere Handbücher für ATW-MBS-02:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 44
OPERATION
Register
Address
1052
1051
1053
1052
1054
1053
1055
1054
1056
1055
1057
1056
1058
1057
1059
1058
1060
1059
1061
1060
1062
1061
1063
1062
1064
1063
1065
1064
1066
1065
1067
1066
1068
1067
1069
1068
1070
1069
1071
1070
1072
1071
1073
1072
1074
1073
1075
1074
1076
1075
1077
1076
11
PMML0419A rev.1 - 05/2016
Description
Status Circuit 1 Run/Stop
Status Heat. OTC Circuit 1
Status Cool. OTC Circuit 1 (*2)
Status Circuit 1: Thermostat Setting Temperature
Status Circuit 1: Thermostat Room Temperature
Status Circuit 1: Water heating Fix Setting Temp
Status Circuit 1: Water cooling Fix Setting Temp (*2)
Status Circuit 2 Run/Stop
Status Heating OTC Circuit 2
Status Cooling OTC Circuit 2 (*2)
Status Circuit 2: Thermostat Setting Temperature
Status Circuit 2: Thermostat Room Temperature
Status Circuit 2: Water heating Fix Setting Temp
Status Circuit 2: Water cooling Fix Setting Temp (*2)
Status DHWT Run/Stop
Status DHWT Setting Temperature
Status Swim.Pool Run/Stop
Status Swim. Pool Setting Temperature
Status AntiLeg. Run
Status AntiLeg.Setting Temperature
Status block menu
Status BMS Alarm
LCD Central Mode
System Configuration
DHWT Temperature
Swim temperature
Value
0: Stop
1: Run
0: No
1: Points
2: Gradient
3: Fix
0: No
1: Points
2: Fix
50~350 (5,0~35,0 ºC)
0~1000 (0,0~100,0 ºC)
0~80 ºC(*3)
0~80 ºC(*3)
0: Stop
1: Run
0: No
1: Points
2: Gradient
3: Fix
0: No
1: Points
2: Fix
50~350 (5,0~35,0 ºC)
0~1000 (0,0~100,0 ºC)
0~80 ºC(*3)
0~80 ºC(*3)
0: Stop
1: Run
0~80 ºC(*3)
0: Stop
1: Run
0~80 ºC(*3)
0: Stop
1: Run
0~80 ºC(*3)
0: No
1: Block
0: No
1: Alarm
0: Local
1: Air
2:Water
3: Full
Bit 0: Circuit 1 Heating Available
Bit 1: Circuit 2 Heating Available
Bit 2: Circuit 1 Cooling Available
(*2)
Bit 3: Circuit 2 Cooling Available
(*2)
Bit 4: DHWT Available
Bit 5: SWP Available
Bit 6: Room thermostat available
Circuit 1
Bit 7: Room thermsotat available
Circuit 2
-80~100 ºC (*1)(*3)
-80~100 ºC (*1)(*3)
Type
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis