FBM-Serie
Technical data
General
Electrical connection
Operating voltage
Relative humidity output
Temperature output
Current draw
Sensor, measurement ranges
Temperature sensor element
Temperature measurement range
Temperature deviation
Humidity sensor element
Relative humidity measurement range
Relative humidity deviation
Long-term stability
Connection conditions
Environmental temperature
RH working range
Storage temperature
Switch-on / start-up time
t
90
Miscellaneous
Sensor protection
Housing
Protection class
Scope of delivery
(*1) At 20°C
(*2) In the range 40...60% RH and 20°C, otherwise +/-5% at 20°C
20
Screw terminals
15...36V DC, depending on total apparent load
4...20mA corresponding to 0...100%
Load resistance 200...500 Ohm
4...20mA corresponding to -20...80 °C
Load resistance 200...500 Ohm
max. 40mA
Integrated temperature sensor
-20...80°C
+/- 0,5 K
(*1)
Capacitive sensor
0...100%
+/- 3% RH
(*2)
+/- 1,0% / year
-20...80°C
10%...95% RH
-20...50°C
< 10 minutes
< 30 seconds
Sintered filter
Plastic housing, pure white
(similar to RAL 9010)
IP 65 (only housing)
Operating instructions, device,
shipping box