ECLARATION OF CONFORMITY
T.Smedegaard A/S hereby declare that these
products are in conformity with:
2006/95/EG, 2004/108/EG
DIN EN 60335-1, DIN EN 60335-2-51
DIN EN 55014-1, DIN EN 55014-2
DIN EN 61000-3-2, DIN EN 61000-3-3
This installation guide gives the basic instructions which are to be observed during installation, operation and
maintenance of the pump. It is therefore imperative that this manual is read by the responsible operator prior
to the installation and should always be kept available at the site. It is not only the general safety instructions
under the "Safety" section that are to be observed but also the specific information provided throughout this
guide.
Application
The SimFlex circulating pumps are used in all types of heating systems. By use of the advanced internal
speed control, the electric automatic regulator adjusts the pump performance according to system needs. This
feature gives both great electrical, and thermal savings together with reduced noise level in the installation.
Pump medium
Clean, none aggressive and none explosive fluids without any solids or fibres. Kinematic viscosity:
Max. 10mm²/s. Higher viscosity will cause pump to regulate improperly. Capacities shown on the data sheets,
8
are measured with water v =1mm²/s at 20ºC. Suitable for water impurity up to 5mg/dm³. Please note: If any
GB
liquid other than water is being pumped, we recommend that you contact T. Smedegaard A/S or one of our
representatives, as the pump characteristics may change.

Technical data

Electrical data:
Serial No.:
Max. working pressure::
Min. static head at 80°C:
Min. static head at 95°C:
SimFlex
type:
15/25/32-40
15/25/32-60
See nameplate
See nameplate
10 bar (1000 kPa)
0,4 - 0,5 bar (40-50kPa)
0,5 - 0,7 bar (50-70kPa)
Ambient temp.
Water temp.
max. [°C]
max. [°C]
95
95
95
95
Minimum water temp. +15°C

Installation Guide

SimFlex
Tommy Andersen. T.Smedegaard A/S
57-59 Sydvestvej, DK-2600 Glostrup
Denmark
Sound pressure level
Max. 40dB(A)