Safety Instruction:
The installation, operation and
maintenance must be carried out by an
electrician suitably trained in hazardous
areas with knowledge of increased safety
explosion protection IEC 60079-14.
The technical data indicated on the
LED luminaires are to be observed.
Changes of the design or
modifications to the LED luminaire
are not permitted
Observe the national electrical
safety rules and regulations during
installation.
No user serviceable parts inside.
No field replaceable parts.
Technical Data:
Category of Application:
32W:
Ex e mb IIC T4 Gb
Ex tb IIIC T135°C Db
II 2GD
64W
Ex e mb IIC T4 Gb
Ex tb IIIC T135°C Db
II 2GD
IECEx / ATEX:
SIRA 12ATEX3217X
IECEx SIR 12.0093X
Rated Input
Voltage:
100-277 VAC 50/60 Hz
Rated Input Current:
32W:
175mA at 230V AC
350mA at 110V AC
64W:
350mA at 230V AC
700mA at 110V AC
Inrush Current
@230VAC
32W:
1A for 6ms
64W:
6A for 50μs
Operating Temp. -20°C to +60°C
Housing:
Marine Grade 316
Stainless Steel IP66/67
Dimensions:
See diagram page
Cable Entries:
Standard 2 OFF M20 x 1.5mm
(M25 x 1.5mm optional)
Terminal block:
Standard: 4-way, max. 4mm²
5 wire thru: 7-way, max. 4mm²
Through cable:
Standard: 3 x 1.5 mm²
5 wire thru: 7 x 2.5 mm²
Tightening
See page 2
Torques:
Weight:
32W:
6.5Kg
64W
11.4Kg
SafeSite® Stainless Steel Linear for ATEX/IECEx
Conformity with Standards
This equipment conforms to the standards specified in
the Declaration of Conformity. It has been designed,
manufactured and tested in accordance with BS EN
9001.
ATEX Directive 2014/34/EU: Equipment and protective
systems intended for use in potentially explosive
atmospheres. EMC Directive 2014/30/EU Directive for
electromagnetic compatibility.
Equipment Application
This lighting equipment is intended for use in a
potentially explosive atmosphere in Zones 1, 21 and 2,
22 to the requirements of ATEX Directive 2014/34/EU.
Mounting the Luminaire
Assemble the mounting bracket to the Luminaire with
two M8 x 1.25 by 16mm bolts. Torque specification:
2.0Nm maximum.
Installation
Ensure that the mains voltage supply is disconnected
before connecting the luminaire. Install the equipment
in accordance with the manufacturer's instructions as
well as any other applicable electric codes.
Always transport and store the equipment in its original
packaging and keep in a dry location. When
unpacking check for any cracks or damage in the
housing or lens. If in doubt, do not install!
NOTE: The cabling used must be suitable for the site
application and/or the site requirements.
When assembling the cable entries for the mains
connection,
always
observe
specifications for the glands used. Unused cable entries
must be closed and sealed by a certified blanking plug.
NOTE: Unused cable entries must be closed off with a
certified blanking plug or stopper. Dust caps must be
removed and replaced with either a suitable cable
gland or certified blanking plug.
The cable entries should be securely tightened to ensure
that the minimum protection rating is achieved. A
locknut is required for each cable gland to securely
hold the cable gland to the end covers. The cable entry
should be rated to a minimum of IP66/67 to maintain the
protection level of the luminaire.
Do not over tighten as the protection rating may be
compromised. Always refer to the gland manufacturer's
data for torque settings.
Cable gland with O-ring min. thread length C = 10mm.
P = M20 x 1.5mm
P = M25 x 1.5mm (suffix 4)
The terminal block is suitable for multi-stranded or single
core wires up to a maximum of 4mm2, strip length
10mm.
The LIVE, NEUTRAL and EARTH connections are clearly
marked on the terminal block or on a label. Push down
at the 'cross point', insert correct wire and release,
ensuring all the conductor has been securely retained.
3 Phase Wiring Connection
Connect the designated load phase (e.g. L1) to L on the
terminal block and the other 2 live phases to
appropriate live terminals (e.g L2 / L3) on the terminal
block as shown in the diagram.
Loop in /out electrical connections:
Connect incoming cable as above then connect the
outgoing cable to the associated adjoining connection
on the terminal block to pass to the next luminaire. The
outgoing cable may also be connected to the terminal
block at the opposite end to the incoming cable (loop
through)
WARNING:
Only single wires to be used on each terminal entry
point.
The improper installation, operation, or maintenance of
these luminaries may result in the invalidation of the
warranty, certificate or declaration of conformity.
Taking into Operation
Prior to operating, check the luminaire for its correct
installation
instructions and other applicable regulations.
WARNING:
Only fully certified equipment may be put into
operation.
Conditions for Use
The supply to the luminaire must include a fuse which is
capable of interrupting a 1.5kA short circuit current.
When used with steel wired armour or braided cable the
basket weave armour or braid is unable to carry the
cable load without fracture. The cable must therefore
be clamped and cleated to prevent pulling on the
cable being transmitted to the cable terminations.
Improper installation or operation of this luminaire may
invalidate the warranty, certificate or declaration of
conformity. For maximum long term reliability and light
the
manufacturer's
output, the luminaire must be installed in free air.
Maintenance
There are no user serviceable parts inside.
This LED luminaire should require a minimum amount of
maintenance. If any unforeseen repairs are required,
please contact Dialight or its authorised representative.
Inspection
Within the scope of maintenance or inspection routine
the following should be included: Protective hoses
covering the connection cables - cable entries must be
free of corrosion.
Perform visual mechanical and electrical inspections on
a regular basis.
We recommend routine checks to be made on a yearly
basis. Frequency of use and environment should
determine this.
It is recommended to follow an Electrical Preventive
Maintenance Program as described in NFPA 70B:
Recommended Practice for Electrical Equipment.
Repairs / Overhaul / Modification
Should the luminaire enclosure be damaged, only a
replacement will be permitted. In case of doubt, the
equipment
inspection/repair. Modifications to the device or
changes of its design are not permitted.
The equipment must be operated according to the
intended purpose in a perfect and undamaged
condition.
Disposal Recycling
When the apparatus is disposed of, the respective
national regulations on waste disposal should be
observed.
WEEE
equipment) registration number W EE/DC2678RY.