9. Technical data

9.4 Temperature measurement

Designation
Temperature sensor type
Measuring cycle and
temperature calculation
Max. difference temperature
Min. difference temperature
Energy calculation from
Absolute temperature
measuring range

9.5 Voltage supply

Designation
Operating voltage
Battery life
9.6 Radio/ Wireless
Designation
Frequency
Log
Transfer power
Transfer interval
60
Value
Pt 500/2 wire
32 s
+102 K oder +147 K
+3 K
0,25 K
0 °C ... 105 °C or 0 °C ... 150 °C (variant dependent - see name plate)
Value
3 V (lithium battery)
up to 12 years
Value
868 MHz
Open Metering Standard (OMS)
10 mW
64 s

Werbung