Check code
Indication on 7-segment display on the outdoor unit
Auxiliary code
01: Compressor 1
P05
02: Compressor 2
01: Compressor 1
P07
02: Compressor 2
P10
Detected indoor unit address
P13
01: TS condition
P15
02: TD condition
P17
P19
Detected outdoor unit number
P20
#0: Element short circuit
#E: Vdc voltage trouble
#1: Position detection circuit trouble
#2: Input current sensor trouble
#3: Motor lock trouble
P22
#C: Sensor temperature trouble (No TH sensor)
#4: Motor current trouble
#D: Sensor short circuit/release trouble (No TH sensor)
#5: Synchronization/step-out trouble
*Put in Fan IPDU No. in [#] mark.
01: Compressor 1
P26
02: Compressor 2
01: Compressor 1
P29
02: Compressor 2
*1 IPDU number information
01: Compressor 1
trouble
02: Compressor 2
trouble
03: Compressor 1 and 2
trouble
08: Fan 1
trouble
09: Compressor 1, Fan 1
trouble
0A: Compressor 2, Fan 1
trouble
0B: Compressor 1 and 2, Fan 1
trouble
135-EN
Check code name
Compressor Vdc trouble
AC detection circuit trouble
Heat sink overheat trouble
Indoor overflow trouble
Outdoor unit flow back trouble detected
Gas leak detection
Discharge temperature TD2 trouble
4-way valve inverse trouble
High-pressure protective operation
Outdoor fan IPDU trouble
IPM short protection trouble
Compressor position detecting circuit trouble
Check code (indicated on the 7-segment display on the outdoor unit) for MiNi-SMMS-e series (MCY-***)
Indicated when SW01 = [1], SW02 = [1], and SW03 = [1].
Check code
Indication on 7-segment display on the outdoor unit
Auxiliary code
A01
Detected Hot water module address
A02
Detected Hot water module address
A03
Detected Hot water module address
E06
Number of indoor units which received normally
E07
E08
Duplicated indoor addresses
E15
E16
00: Capacity over 01 or more: No. of connected units
01: Other line outdoor connected
E20
02: Other line indoor connected
E31
IPDU quantity information *1
F04
F06
01: TL1 sensor
F07
03: TL3 sensor
F08
01: TS1 sensor
F12
03, 04: TS3 sensor
F13
F15
F16
F23
F24
F31
H01
H02
H03
H05
H06
H07
H08
01
H16
01
L04
L06
Number of indoor units with priority
L08
L10
L23
02
L29
IPDU quantity information *1
L30
Detected indoor unit address
P03
P04
– 68 –
Check code name
Flow switch operation trouble
Water temperature decrease trouble
Activation of water heat exchanger frost protection
Decrease of number of indoor units, or HWM unit only
Indoor / Outdoor communication circuit trouble
Duplication of indoor addresses
No indoor unit during automatic addressing
Number of connected capacity over / indoor units
Other line connected during automatic addressing
IPDU communication trouble
TD sensor trouble
TE sensor trouble
TL1 or TL3 sensor trouble
TO sensor trouble
TS1 or TS3 sensor trouble
TH sensor (Board installed) trouble
Outdoor temp. sensor miswiring (TE, TL1)
Outdoor pressure sensor miswiring (Pd, Ps)
Ps sensor trouble
Pd sensor trouble
Outdoor program trouble
Compressor breakdown
Compressor trouble (Lock)
Current detective circuit system trouble
TD sensor trouble
Low-pressure protective operation
Oil level down detection
TK sensor trouble for oil level
Oil level detector circuit trouble
Outdoor system address duplicated
Duplication of indoor units with priority
Indoor group / Address unset
Outdoor capacity unset
SW setting trouble when connecting to HWM unit
IPDU quantity trouble
External interlock of indoor unit
Discharge temp TD trouble
High-pressure switch trouble