Emerson TCLE series Einbauanleitung
Emerson TCLE series Einbauanleitung

Emerson TCLE series Einbauanleitung

Expansionsventile

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 2
TCLE, TJRE, TERE, TIRE, THRE
General information and technical data
• Refrigerants: see nameplate
• Evaporating Temperature Range:
a) for valves with pressure limitation (MOP): see
nameplate
b) for valves without pressure limitation:
+30° C to -45° C
• Max. Working Pressure PS: 31 bar
• Safe Working Temperature: 80° C
• Marking:
!
Safety instructions
• Read
installation
instruction
Failure to comply can result in device failure,
system damage or personal injury.
• It is intended for use by persons having the
appropriate
knowledge
and
opening any system make sure pressure in
system
is
brought
to
and
atmospheric
pressure.
Do
refrigerant into the atmosphere.
• Do not use on service conditions or fluids not
specifically cataloged, without prior approval of
Alco Controls.
Installation (Fig. 1)
1 Power Assembly
2 Remote Bulb
3 External Equalizer
Connection
4 Seal Cap
5 Body Flange Gasket
6 Cage Assembly
1. Valves may be installed in any position, but
should be located as close as possible to
distributor or evaporator inlet.
T_S__65022__R04.doc
Installation Instructions
®
Thermo
Expansion Valves
2. Install line connections to valve so its flow
arrow corresponds to flow direction on flange.
On valves with solder connections remove cap
screws, power assembly, cage assembly and
gaskets prior to brazing.
3. Assemble valve after brazing, according to Fig
1, making sure that lugs of spring carrier line up
with slots inside power assembly.
4. Tighten
specification 35 Nm. Overtorqueing may result
in valve body damage.
5. Attach remote bulb to suction line as close to
evaporator outlet as possible in a horizontal run
and fix it, normally at the 4 or 8 o'clock
thoroughly.
position. Clean surface of suction line before.
6. Connect one end of external equalizer line (OD
= 6 mm = ¼ inch) to valve. Connect other end
to suction line slightly downstream from remote
skill.
Before
bulb location and position it so that it cannot
syphon oil from the suction line.
remains
at
7. Check for leaks, sufficient system refrigerant
not
leak
any
and be sure no flash gas is present.
Superheat Adjustment (Fig. 2)
ALCO Thermo
preset for optimum superheat settings. This setting
should be modified only if absolutely necessary. The
readjustment should be at the lowest expected
7 Body Flange
evaporating temperature:
Gasket
1. Remove seal cap (1) on side of valve.
8 Seat Gasket
2. Turn adjusting stem clockwise to increase
9 Body Flange
superheat and counter-clockwise to decrease it.
10 Cap Screws
Allen key X 99999 (2).
11 Lugged Spring
3. Reinstall seal cap. Wait 20 minutes before
Carrier
further adjustments.
4. If refrigerant escapes use allen key X99999 (3)
to fix spindle gasket.
Replacement for 03
Emerson Electric GmbH & Co. OHG
GB
Heerstr.111 – D-71332 Waiblingen
Tel.: 07151 509-0 - Fax.: -200
cap
screws
evenly
to
torque
-Expansion Valves are factory
Date: 21.07.2009
www.emersonclimate.eu
Pressure
Evaporating temperature °C
Valve
Refri- changes +10
Series gerant per turn
(bar)
R 134a
0,05
0,4
R 22
0,05
0,3
TCLE R 404A
0,05
0,2
R 407C
0,05
0,2
R 507
0,05
0,2
TJRE R 134a
0,038
0,3
TERE, R 22
0,038
0,2
TIRE, R 404A
0,038
0,2
THRE R 407C
0,038
0,2
R 507
0,038
0,2
Note
1. Foreign particles in Thermo
diaphragm failure, flooding or starving. Use of
an ALCO Filter Drier is strongly recommended.
2. Protect valve against excessive vibrations as it
may result in bulb tubing breaking.
Leakage test:
After completion of installation, a test pressure must
be carried out as follows:
- According to EN378 for systems which must
comply with European pressure equipment directive
97/23/EC
- To maximum working pressure of system for other
applications
Warning:
- Failure to do so could result in loss of refrigerant
and personal injury.
- The pressure test must be conducted by skilled
persons with due respect regarding the danger
related to pressure.
0
-10
-20
-30
-40
Static superheat changes
per turn of stem (K)
0,5
0,6
0,9
0,3
0,4
0,5
0,7
1,0
0,3
0,3
0,4
0,6
0,8
0,3
0,4
0,6
0,3
0,3
0,4
0,5
0,7
0,4
0,5
0,7
0,3
0,3
0,4
0,5
0,7
0,2
0,3
0,3
0,5
0,6
0,2
0,3
0,4
0,2
0,2
0,3
0,4
0,5
-Valve may cause
PCN 862157

Werbung

loading

Inhaltszusammenfassung für Emerson TCLE series

  • Seite 1 Emerson Electric GmbH & Co. OHG Installation Instructions ® Heerstr.111 – D-71332 Waiblingen Thermo Expansion Valves Tel.: 07151 509-0 - Fax.: -200 TCLE, TJRE, TERE, TIRE, THRE www.emersonclimate.eu General information and technical data 2. Install line connections to valve so its flow •...
  • Seite 2 Emerson Electric GmbH & Co. OHG Einbauanleitung ® Heerstr.111 – D-71332 Waiblingen Thermo -Expansionsventile Tel.: 07151 509-0 - Fax.: -200 TCLE, TJRE, TERE, TIRE, THRE www.emersonclimate.eu Beschreibung und technische Daten Oberteil Ventileinsatz 3. Hutmutter wieder aufsetzen. Vor einer weiteren • Kältemittel: siehe Typschild Dichtungen entfernen.
  • Seite 3 Emerson Electric GmbH & Co. OHG Instructions d’Installation Heerstr.111 – D-71332 Waiblingen Détendeur thermostatique Tel.: 07151 509-0 - Fax.: -200 TCLE, TJRE, TERE, TIRE, THRE www.emersonclimate.eu Données techniques 3. Détendeur à braser, démontez train Variation Temp. d'évaporation °C Série Fluide de press. +10 •...
  • Seite 4 Emerson Electric GmbH & Co. OHG Instrucciones de Instalacion Heerstr.111 – D-71332 Waiblingen Válvula de Expansion Termostatica Tel.: 07151 509-0 - Fax.: -200 TCLE, TJRE, TERE, TIRE, THRE www.emersonclimate.eu de fijación, el elmento termostático, el conjunto 4. Si se produce una fuga del refrigerante utilice Datos técnicos...
  • Seite 5 Emerson Electric GmbH & Co. OHG Istruzioni per l’installazione Heerstr.111 – D-71332 Waiblingen Valvola d’espansione termostatica Tel.: 07151 509-0 - Fax.: -200 TCLE, TJRE, TERE, TIRE, THRE www.emersonclimate.eu che non vi siano altre parti montate oltre allo 4. Per evitare perdite di refrigerante, utilizzate Dati tecnici zoccolo.
  • Seite 6 Emerson Electric GmbH & Co. OHG Installatievoorschrift ® Heerstr.111 – D-71332 Waiblingen Thermo -Expansieventielen Tel.: 07151 509-0 - Fax.: -200 TCLE, TJRE, TERE, TIRE, THRE www.emersonclimate.eu 3. Na solderen het ventiel weer in elkaar zetten Toepassing Verdampingstemp. °C Drukverand. overeenkomstig de afbeelding van Fig. 1.
  • Seite 7 Инструкция по установке Emerson Electric GmbH & Co. OHG ТРВ® серий Heerstr.111 – D-71332 Waiblingen Tel.: 07151 509-0 - Fax.: -200 TCLE, TJRE, TERE, TIRE, THRE www.emersonclimate.eu Технические характеристики 3. Соберите вентиль после пайки в • Хладагент: смотри маркировку на ТРВ...
  • Seite 8 Emerson Electric GmbH & Co. OHG Heerstr.111 – D-71332 Waiblingen TCLE, TJRE, TERE, TIRE, THRE Tel.: 07151 509-0 - Fax.: -200 www.emersonclimate.eu Fig. 1: Fig. 2: > 10 Nm < 15 Nm < 15 Nm T_S__65022__R04.doc Replacement for 03 Date: 21.07.2009...

Diese Anleitung auch für:

Tjre seriesTere seriesTire seriesThre seriesThermo tcleThermo tjre ... Alle anzeigen