Herunterladen Inhalt Inhalt Diese Seite drucken

Connection Instructions; Electrical Connections - Daikin E2MV03B6 Installationsanleitung

Motorisierter ventilsatz
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 8
Technical features
Action/Control
Proportional (0...10 V, 0...5 V or 5...10 V)
Maximum stroke
4 mm
Power supply
50/60 Hz 24 VAC ±15%
Inlet impedance
80 k.
Apparent Consumption
2.7 VA powered - Active 2 W
M
CTRL
COM
24V -
Power Supply - Red (RD) + 24V and Common (CM).
Nominal force
120 N +30%
Stroke time
15 s/mm
Protection
IP40 (EN 60529)
Cover/shaft material
PA66-Glass+(30% Kelon A FR CETG/300-V0)
Ring nut material
Brass CuZn40Pb2
Coupling
M30 x 1,5
Cover colour
RAL 7035
Ambient operating conditions
0-50°C without condensation
Storage conditions
-20 + 65°C without condensation
Maximum fluid temperature
95 °C

Electrical connections

2 m flexible cable Ø 4.5 mm
Operating status
LED
Noise level
<30 dB(A)
Weight
0,15 kg
Installation
Never use the actuator as an assembly lever (figure 6d)
Electrical connections
The wiring diagram is reported on the outside of the motor cover.
The colours of the cables may vary. Refer to the label of the wiring
diagram or the instruction sheet that comes with the motor.
For the 0-10 V proportional actuator:
Positive control signal (+) White cable;
Negative control signal (-) Black cable.
E2+E4MV03~10A6
Kit of the motorized ON/OFF valve
4PW17554-4
COM
=
Common
RD
=
Red
BK
=
Black
BU
=
Blue
WH
=
White

Connection instructions

In case of assembly or maintenance make sure that:
!
The power is off to avoid possible damage to the appliance and
persons.
!
Do not touch, connect or disconnect leads when the power is on.
During the electrical connection, follow the instructions below:
!
Before carrying out the connections, make sure the power has
been disconnected or turned off to avoid potential damage to the
material or persons.
!
Make sure that the power supply matches the specifications on
the actuator cover.
All the connections must comply with current laws and standards and
must be carried out by specialised personnel.
NOTES
!
The control signal comes from the FWEC3A control panel: refer
to its manual to view the instructions and electrical connections.
!
Daikin units do not have a 230V-24V transformer.
You need to provide for a separate power supply.
notes
Installation manual
2

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis