SEQUENCE OF THE REGENERATION ON IMMEDIATE VOLUME PROGRAM
NO.
OPERATIONS KEYS TO PRESS
TIME
1
ADVANCE
TIME
2
ADVANCE
TIME
3
PROGRAM
4
ADVANCE
PROGRAM
5
ADVANCE
PROGRAM
6
ADVANCE
PROGRAM
7
ADVANCE
PROGRAM
8
ADVANCE
PROGRAM
9
ADVANCE
PROGRAM
10
ADVANCE
PROGRAM
11
ADVANCE
PROGRAM
12
ADVANCE
PROGRAM
13
TIME
PROGRAM
14
ADVANCE
PROGRAM
15
ADVANCE
PROGRAM
16
ADVANCE
17
PROGRAM
PROGRAM
11
ADVANCE
CAUTION:
When carrying out operations 7-8 to set the value of softened water, proceed as follows:
DOUBLE 35-50-65:
DOUBLE-PLUS 85-550:
In this way the displays will decrease by one number every 5 litres for the models DOUBLE 35-50-65 and by one number every 100 litres for the
models DOUBLE-PLUS 85 ÷ 550.
DATA ON DISPLAY
Press key A "TIME" then
08.56
C "ADVANCE" to adjust the minutes
Press key A "TIME" then
08.56
C "ADVANCE" to adjust the hours.
08.56
Press key A "TIME" to store data set
Press key B "PROGRAM" and
0.2 30
DO NOT change the DATA displayed and continue.
Press key B "PROGRAM" and
0.2 30
DO NOT change the DATA displayed and continue.
Press key B "PROGRAM" and
FF.04
DO NOT change the DATA displayed and continue.
Press key B "PROGRAM" then
48 0.0
C "ADVANCE" to adjust the litres of softened water
Press key B "PROGRAM" then
48 0.0
C "ADVANCE" to adjust the litres of softened water
Press key B "PROGRAM" and
00.00
DO NOT change the DATA displayed.
00.00
ditto
Press the key B "PROGRAM" then
AA 20
C "ADVANCE" and adjust 20
Press key B "PROGRAM" then
AA dd
C "ADVANCE" until the VOLUME led lights up
Press key B "PROGRAM" then A "TIME"
1C 06
to access the times. With the key C "ADVANCE"
you can change the data
Press key B "PROGRAM".
2C 30
With the key C "ADVANCE" you can change the data
Press key B "PROGRAM".
3C 30
With the key C "ADVANCE" you can change the data
Press key B "PROGRAM".
4C 10
With the key C "ADVANCE" you can change the data
4d 10
Press key B "PROGRAM"
For the models 85 ÷ 550
AA 10
press C "ADVANCE" and adjust 10.
divide the actual value by 5. See table page 37
divide the actual value by 100. See table page 38 - 39
WHAT TO DO ON KEYBOARD
MEANING OF DATA SET
HOURS and MINUTES of the clock
e.g. 08.56
These data are set for other
PROGRAMS
e.g. PLUS 550 with 30°F
set 112000:100 = 1120
VOLUME softened water:
e.g. Double 65 with 30°F
set 13700 : 5 = 2740
These data are set for other
PROGRAMS
Reading report of counter, one pulse
every 5 litres for Double 35-50-65
IMMEDIATE VOLUME PROGRAM
Cycle no. 1 backwash
see TIMES TABLE
Cycle no. 2 brine suction
see TIMES TABLE
Cycle no. 3 slow rinse
see TIMES TABLE
Cycle no. 4 rapid rinse
sending water to salt container.
See TIMES TABLE
FINAL PROGRAMMING STEP
Report for litre counter reading,
one pulse every 100 litres
35