TECHNICAL CHARACTERISTICS OF THE CONTROL UNIT
1) Power supply: 12 V DC
2) ABS case
3) Protection class: IP 40
4) Display of temperature and operating status via 32-dot LEDs
5) Setting of parameters and functions via 7-key conductive membrane keypad
6) Operating range 5 to 30 °C with resolution of 0.1°C and precision of ± 1.5 %
7) NTC temperature measurement sensor with precision of ± 1%.
8) Connection via printed circuit terminal board
9) Operating mode selection via 10-pole dip switch
10) Operating temperature 0/40 °C
11) Storage temperature -20/+70 °C
TECHNICAL CHARACTERISTICS OF POWER UNIT
1) Power supply 230 V AC
2) ABS case
3) Protection class: IP 20
4) Connection via printed circuit terminal board
5) 6 x 8 (2) A 250 V AC relays to control: I-II-III fan speed, cold and hot water solenoid valve, electrostatic filter and/or additional
resistor
6) 2 x optoinsulated inputs for remote seasonal changeover, reducing set point reduction or turning off the control unit
7) 1 x temperature sensor for measuring water temperature
8) Operating temperature 0/40 °C
9) Storage temperature -20/ + 70 °C
DIGITAL CONTROL UNIT INSTRUCTION SHEET
Wall-mounted digital control unit

Installation

The wall-mounted control unit comes complete with all accessories necessary for correct installation on the wall or in a built-in box. The
accessory consists of two main parts: the control unit to be installed on the wall of the room to be air conditioned and the electronic
power unit to be installed on the fan coil. The two parts are connected via a bipolar nonpolarized cable with a maximum length of 30
m. The wall-mounted unit houses the room temperature measurement sensor. For optimum operation of the thermostat, position the
control unit at a height of 1.5 metres from the floor, away from sources of heat and currents of air. Avoid mounting on outside walls
as their temperature could falsify the temperature reading of the control unit.
Preparing the electrical installation
- to connect the wall-mounted control unit to the appliance, a bipolar cable with 0.5 mm 2 cross section wires must be installed. To facilitate
connection to the control unit terminal board, leave 100 mm of cable protruding from the wall.
Wall mounting pag. 39
To install the wall-mounted control unit, proceed as follows:
- open the control unit by separating the front panel 1 from the base 2
- fix 2 anchors to the wall positioned so as to allow the connection cable to be passed through the top slit (fig. 2)
- pass the cable through the slit and connect using the poles of terminal board MC1 on the electronic board (fig. 2)
- rest the front panel on the base and fix the control unit using the two screws provided
- fix the two screw head covers 5 and 6 by pressing lightly with the fingers.