5.0 APPROVED ACCESSORY ITEMS
The XTR-ULTRA Refrigerant Recovery Machine requires the proper accessory items to ensure the
best performance. The following items are specifically identified to ensure safety and operational
requirements are met. Check with your wholesaler to ensure that the proper selections have been
made.
5.1 REFRIGERANT HOSES should be made with approved materials, should be as short as
possible to perform the required operations and should have shut-off devices within 300mm of the
ends.
Approved hoses are: Refrigerant hoses with UL recognition and 27580 Kpa (275 bar/4000 PSI)
burst strength.
5.2 RECOVERY CYLINDERS should be approved and have an appropriate pressure rating for the
refrigerant being recovered. Choose the size that is right for the job.
5.3 FILTERS should be selected to protect the Inlet of the recovery machine from particles of
dust, metal and other foreign materials that may be present in the refrigeration system. If servicing
a system with a burned out compressor, 2 or more FILTERS in series may be necessary, and they
should be discarded immediately after use.
Approved filters are: Filters UL recognized/CSA listed for Refrigeration Service.
5.4 EXTENSION CORDS, when necessary, should be as short as possible and should contain size
16 AWG (1.291 mm) or larger conductors. This is necessary to avoid over-heating during periods of
high current draw and minimize the risk of fire. The longer the extension cord required at the work
site, the larger the conductor size should be particularly for runs over 10m.