Herunterladen Diese Seite drucken

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

DMD is a differential pressure transmitter for air and neutral gases. The unit has LED-display and
built-in controlling function. The main application is for pressure control in air handling systems.
Selectable measuring range 0...100, 0...300,
*
0...500, 0...1000 Pa
Pressure signal output 0...10 V and 4...20 mA
*
Controls output 0...10 V
*
Function
The differential pressure transmitter DMD is based
on microprocessor technology and has a logical
menu system.
Setting of the working range, damping, and zero-
point adjustment is done using buttons under the
lid.
Controlling function
DMD-C has a built-in controller with PID-function.
All parameters are adjustable. The control function
has a 0...10 V DC output signal.
Measuring technique
Pressure measurements are obtained by means of
a sensor that uses a ceramic measuring beam.
The differential pressure affects a membrane that
works directly against the measuring beam. A
thick-film resistor is mounted in the bending area of
the measuring beam. When the measuring beam
bends the resistance value changes. The change
is converted to a proportional output signal via the
built-in electronics.
Differential pressure transmitter with built-
in controller 0...100/ 300/ 500/ 1000 Pa
Adjustable damping of the measuring signal
*
Zero-point adjustment
*
The small number of moving parts in the
transmitter, permits a high degree of accuracy and
short response time. Another important quality is
that the ceramic element has very good long-term
stability.
Adjustable working range
DMD can easily be set between the working ranges
0...100, 0...300, 0...500, 0...1000 Pa.
Electronical damping
The pressure transmitter has electronic damping to
counteract rapid fluctuations in the output signal,
this function is adjustable 0...20 s.
Zero-point adjustment
The output can easily be zero-point adjusted, see
overleaf.
DMD is supplied complete with connection set
containing two pressure outlets and 2 m of hose.
DMD-C
section position
2-330
Nov 13

Werbung

loading

Inhaltszusammenfassung für Regin DMD-C

  • Seite 1 Adjustable working range Controlling function DMD can easily be set between the working ranges DMD-C has a built-in controller with PID-function. 0...100, 0...300, 0...500, 0...1000 Pa. All parameters are adjustable. The control function Electronical damping has a 0...10 V DC output signal.
  • Seite 2: Technical Data

    4 Output 0...10 V DC (sensor) 5 Output 4...20 mA (sensor) 6 Output 0...10 V (controller) 7 Net A (only DMD-C-LON) 8 Net B (only på DMD-C-LON) 9 Ground Head Office Sweden Sales Offices Phone: +46 31 720 02 00...
  • Seite 3: Installation

    Tryck på knapp Up tills displayen visar -08. VIKTIGT: Läs denna instruktion Tryck på Enter varvid displayen skall visa 000. Tag av frontlocket. Montera DMD-C mot ett fast, icke vibrerande innan produkten monteras och Dämpning används om trycksignalen upplevs som orolig. Dämp- underlag.
  • Seite 4 Press Up until the display shows -08. Remove the front cover. Mount the DMD-C on a steady, non-vibra- Press Enter and the display will show 000. ting surface. The unit should preferably be mounted vertically with Damping is used If the pressure signal is experienced as being the pressure connections pointing downwards.
  • Seite 5: Caractéristiques Techniques

    Appuyez sur Enter et l’affichage montre 000. cordement de ce produit Ôter le capot frontal. Monter le DMD-C sur une surface stable et Utiliser le lissage si le signal de pression est trop instable. Le sans vibrations. Il est préférable de monter l’unité verticalement DMD-C fait alors un calcule continu de la valeur moyenne pendant avec les connexions de pression vers le bas.
  • Seite 6: Montage

    Druckanschlüssen nach unten montiert werden. Die Dämpfung wird eingesetzt, wenn sich heraus stellt, dass Benutzen Sie die beiden Schraubvorrichtungen am Unterteil des Geräts. ein Drucksignal nicht stabil genug ist. Der DMD-C nimmt dann eine kontinuierliche Mittelwertberechnung für die eingestellte Verdrahtung Dämpfungszeitdauer vor und benutzt den berechneten Wert...