RIN-APU24 – MOUNTING INSTRUCTIONS
Special Case 3
Fig. 3 pertains to the wiring of the RIN-APU24 to an XP502
powering XC5010C controllers equipped with internal
modules and connected with Distributed I/O modules. In such
a case, two RIN-APU24 units are required.
The first RIN-APU24 is wired to the XP502, which powers
only the XC5010C controller. Repeat: It is not allowed to
power any other device with the XP502.
The second RIN-APU24 is wired to one or more XSL511
L
W
connector modules, which power the Distributed
ON
ORKS
I/O modules. The wiring of the second RIN-APU24 to relay K1
of the XP502 ensures that the power supply of the Distributed
I/O modules will be switched OFF whenever the XP502 is
switched OFF.
(1) RIN-APU24-2
1 L
AC
1.6 A
230V~
(+6%/-10%)
50...60 Hz
DC
BATTERY
2 N
3 PE
SWITCHED POWER
SUPPLY
C4
NC6
(2) RIN-APU24-2
1 L
AC
1.6 A
230V~
(+6%/-10%)
50...60 Hz
DC
BATTERY
2 N
3 PE
SWITCHED POWER
SUPPLY
C4
NC6
TO OTHER XSL511s
OF THE SAME CONTROLLER
Fig. 3. XC5010C with internal and DIO's
XCL5010
Fig. 4 pertains to the wiring of the RIN-APU24 to an XCL5010
controller.
RIN-APU24-2
1 L
AC
1.6 A
230V~
(+6%/-10%)
50...60 Hz
DC
BATTERY
2 N
3 PE
SWITCHED POWER
SUPPLY
C4
NC6
Fig. 4. XCL5010 + RIN-APU24
IMPORTANT
1.
Terminals 3 through 14 of the XCL5010 are not needed
and are not to be used as auxiliary terminals.
2.
In the case of the XCL5010, terminals 4, 5, and 6 of the
RIN-APU24 are not used.
XL100C
Fig. 5 pertains to the wiring of the RIN-APU24 to an XL100C
controller.
MU1Z-0977GE51 R1112
XP502
8, 9
1
4 A
24 Vdc
2
10, 11
4 A
3
4
5
BATTERY
OPERATION
6
NO5
7
8
16
8, 9
17
4 A
24 Vdc
18
10, 11
4 A
XSL511
1
2
BATTERY
3
OPERATION
4
5
6
NO5
24V
XCL5010
8, 9
1
4 A
24 Vdc
2
10, 11
4 A
3
4
BATTERY
OPERATION
14
NO5
1 L
1.6 A
230V~
(+6%/-10%)
50...60 Hz
2 N
3 PE
SWITCHED POWER
K1
FALCON
Fig. 6 pertains to the wiring of the RIN-APU24 to a FALCON
controller.
1 L
1.6 A
230V~
~
(+6%/-10%)
50...60 Hz
2 N
3 PE
SWITCHED POWER
WATCHDOG
max.
24 V~
3 A
24 Vac
LION
24 Vac
Fig. 7 pertains to the wiring of the RIN-APU24 to a LION
controller.
IF EARTH GROUNDING AS PER
EN60204-1 IS REQUIRED, REFER
TO APPENDIX 1 of LION -
Installation & Commissioning
Instructions (EN1Z-0921GE51).
1 L
AC
1.6 A
230V~
(+6%/-10%)
50...60 Hz
2 N
3 PE
SWITCHED POWER
SUPPLY
2
COMMON
RIN-APU24-2
AC
4 A
4 A
DC
BATTERY
BATTERY
SUPPLY
OPERATION
C4
NC6
NO5
Fig. 5. XL100C + RIN-APU24
RIN-APU24-2
AC
4 A
4 A
DC
BATTERY
BATTERY
SUPPLY
OPERATION
C4
NC6
NO5
Fig. 6. FALCON + RIN-APU24
71
75
71
LION
72
76
72
CONTROLLER
CLIOxx
73
77
73
74
78
74
RIN-APU24-2
8, 9
4 A
24 Vdc
10, 11
4 A
DC
BATTERY
BATTERY
OPERATION
C4
NC6
NO5
Fig. 7. LION + RIN-APU24
55
56
57
58
59
60
61
62
63
64
}
65
24 V
300 mA
66
}
67
10 V
10 mA
68
69
70
8, 9
}
71
24 Vac
+/- 20% or
24 Vdc
72
24...28 Vdc
10, 11
FALCON
8, 9
24 V~
1
24 Vdc
24 V-0
2
10, 11
3
4
5
6
7
8
75
71
75
76
72
76
CLIOxx
77
73
77
1 2
78
74
78
to
FIELD DEVICES
230 V~

Werbung

loading

Diese Anleitung auch für:

Rin-apu24