Mounting and Connection Instructions
Flash lamp - red
Item no. 042100.17
Flash lamp - yellow
Item no. 042105.17
042100.17
Mounting
Guidelines
- Alarm signaling devices must be installed so that
- They are easily visible,
- They cannot be affected by lightening,
- They cannot be reached without using e.g. a ladder.
- The housing must be attached directly to the wall without a space
between.
- Only use stainless steel screws.
For detailed information, please refer to our leaflet on "Intrusion detection
systems - manual for planning and projecting" (P03062-15-000-xx)
The flash lamp can be installed either on top or underneath.
The installation height is of importance. The higher the alarm device is
installed, the more easily visible is the flash lamp when it is installed
underneath.
Determine the degree of visibility by testing.
With direct climatic influence we recommend to mount the flash lamp
on top.
Bracket item no. 042120
(accessories)
The flash lamp is intended for attaching to the wall and can either stand
or be suspended using the bracket. This is necessary e.g. if the flash
lamp requires mounting on eaves, ledge or equivalent.
The following illustration shows the varying possibilities.
Suspended - 2 positions as illustrated
According to VdS-guidelines, lines which are layed
outside of the secured area must not be identifiable as a
part of the IAS. If this is not possible due to structural
conditions, the lines must be layed in a closed piping
system.
Honeywell Security Group
Novar GmbH
Johannes-Mauthe-Straße 14
D-72458 Albstadt
www.honeywell.com/security/de
042105.17
Final assembly
- Secure the cable with a pull relief.
- In order to prevent leakage current, the connections must be coated
- Attach the top part of the housing and screw tight.
Standing 2 positions
- Insert the seals in the screw openings.
Technical data
Rated operating voltage
Operating voltage range
Current consumption at U
Flashing frequency
Environmental protection class as per VdS
Protection class as per DIN 40 050
Operating temperature range
Storage temperature range
Dimensions W x H x D
Color
Subject to change
Set-up
1
3
2
1
Holes for
- wall attachment
- or bracket
2
Connection PCB
Connection diagram
DB1
R
A
TA1
with a protective lacquer (also those which are not occupied).
Please ensure that the leads are covered with a protective lacquer
as far as the insulation.
Only tighten the screws slightly (if possible by hand). Do not
use a battery-operated screwdriver with uncontrolled torque.
If the screws are screwed too tight, the housing may be
damaged.
NORM
Housing
Luminous field
without notice
6
1
4
5
3
Cover contact
4
Cable entry with gasket
5
Pull relief
6
Cable to flash lamp
End of line resistor:
DB1 closed
R = 0R
A
DB1 open
R = 12k1
A
The end of line resistor R is mounted
A
on the soldering terminals and, if
required, can be by replaced by
-
another terminating resistance.
The end of line resistor must be on the
+
last user.
12 V DC
10 V to 15V DC
400 mA
ca. 2 Hz
IV
IP 65
-25 °C to +60 °C
-25 °C to +70 °C
188 x 142 x 92 mm
traffic white
(similar RAL 9016)
Red or yellow