After exit from the configuration level (see page 43, the controller is
re-initialized (all display elements are lit) and changes over to normal operation
(operating level).
g
Leading zeros are not displayed (ex.: display 400 with code 0400)
Configuration example 1 (code 0400):
KS40-1 as a signaller with
switch-over contact for 2-stage burner:
Measuring range 0...200°C,
Resistance thermometer Pt 100,
Reaction at sensor break
as process value higher than set-point.
Configuration example 2 (code 2120):
KS40-1 as 3-point stepping controller:
Connection to pressure transmitter P30/W,
Measuring range 0,00...1,00 bar,
Reaction at sensor break as process value
smaller than set-point.
Function: Signaller with switch-over contact
CAUTION: The two relays
1 and 2 are coupled, i.e.
the contacts have
switch-over function.
Ensure that the two relays
are not energized or
de-energized
simultaneously. Exception:
de-energized condition.
Settings:
Switching differences:
Limit value OUT3:
Signalling LEDs:
Parameter:
9499-040-63201
ON
OUT1
Sd1
=
OUT2
-X
OFF
W
ON
Sd1 / Sd2: in physical values
The relay is de-energized when exceeding the limit.
Upper limit value H. 1 : in units of phys. quantity.
Switching difference HYS. 1 : in units of phys.quantity
LED1:
lit when OUT1 is energized
LED2:
lit when OUT2 is energized
OK-LED: lit, unless the limit value is reached
see chapter 13 "Parameter level"
45
Configuration level
123. 8
123. 8
Con1
123. 8
123. 8
Con1
W
OFF
Sd2
ON
H. 1
Limit OUT3
HYS. 1
KS40-1 -weishaupt-
400
2120
X
W
OFF