Baumer TER8 Betriebsanleitung Seite 10

Front-flush and low-invasive resistance thermometers
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Front-flush and low-invasive resistance
12.2 Transmitter
Power supply
Voltage supply range
Reverse polarity
protection
Power-up time
Factory settings
Output range
Current limits
Output at
sensor fault
Damping
10 / 28
Temperature measurement
TER8
thermometers
8 ... 35 V DC
Yes
< 20 s
0 ... 150 °C
Lower: 3.5 mA
Upper: 20.5 mA
23 mA
0.0 s
Operating Instructions
Output signal
Current output
Shunt resistance
Min. output span
Sampling interval
Damping
Max. conversion error
Max. output error
Temperature drift
(by ambient)
4 ... 20 mA (2-wire)
Rs ≤ 680 Ohm
(Vs = 24 V DC)
Rs ≤ (Vs – 8 V) / 0.023 A
25 °C
0.5 s
0.0 ... 30.0 s
(programmable)
± 0.25 °C
± 0.1 % FS (± 0.016 mA)
< ± 0.003 % FS / °C typ.
< ± 0.01 % FS / °C max.
www.baumer.com