Herunterladen Inhalt Inhalt Diese Seite drucken

Process Fault Messages - Endress+Hauser RIA261 Betriebsanleitung

Digitaler feldanzeiger
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 4
10 Fault-finding
Fault mes-
sage code
E 090
Loop current too low. To store ope-
rating data a mimimum of 3.6 mA
has to be provided on the input.
E 101
The hardware required to store the
operating parameters is defective.
E 102
Checksum of operating parameters
is invalid or the software version
does not correspond with the ope-
rating data. Possible cause is a
power failure during a parameter
save procedure.
E 103
The calibration values for the ana-
logue input are faulty. Possible
cause is a power failure during cali-
bration, an uncalibrated unit or a
defective unit.
E 106
Warning: Due to an installation
fault an incorrect setting up of the
display range/scale was made
(lower and upper values are identi-
cal).
E 111
The hardware for saving the opera-
ting parameters is defective.
42

10.2 Process fault messages

Faults that occur during the unit's self test or during continuous opera-
tion are immediately shown on the display. Fault messages that can be
acknowledged are deleted by operating a push button.
Cause
Digital field display
Cure
Check loop circuit.
Please exchange the unit.
A PRESET is automatically initiated by
operating the "E" push button. This means
that all parameters are returned to the fac-
tory default values. Any special customer
specific settings made at the factory are not
taken into consideration!
Please exchange the unit.
Please correct the values.
Please exchange the unit.

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis