Herunterladen Inhalt Inhalt Diese Seite drucken

S+S REGELTECHNIK HYGRASGARD series Bedienungs- Und Montageanleitung Seite 7

Außenfeuchtefühler
Vorschau ausblenden Andere Handbücher für HYGRASGARD series:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

G
Installation and Commissioning
Temperature
measuring ranges
(adjustable)
  0...+50 °C (default)
–20...+80 °C
–35...+75 °C
–35...+35 °C
Service
display ⁄ output
(adjustable)
Display of °C and % RH,
output of set
measuring values per DIP 1-5
(service mode for
°C and % RH settings)
Display and output
of set measuring values
per DIP 1-5
Display
service mode
The service mode simultaneously displays (alternately in the first and
second lines) the actual temperature and the actual humidity (relative
humidity).
By default, the display alternates between the actual temperature and the
actual humidity (relative humidity). In this case, the first line displays the
value while the second line displays the corresponding unit: Temperature
in °C ⁄ Relative humidity in % r.H.
For improved legibility, backlighting is provided.
Type ⁄ WG01
Measuring Range
Humidity (switchable)
KAVTF
K AV T F -I
0 ...100 % r. H. ( default )
0...50 g ⁄ kg
0...80 g ⁄ kg
0...50 g ⁄ m
0...80 g ⁄ m
0...+50 °C
–20...+80 °C
0...85 kJ ⁄ kg
K AV T F -I _ DISP L AY
(8 x as above)
K AV T F - U
(8 x as above)
K AV T F - U _ DISP L AY (8 x as above)
AAVTF
A AV T F -I
(8 x as above)
A AV T F -I _ DISP L AY
(8 x as above)
A AV T F - U
(8 x as above)
A AV T F - U _ DISP L AY (8 x as above)
Accessories
Metal sinter filter, Ø 16 mm, L = 32 mm, exchangeable, stainless steel V4A (1.4404)
SF-M
WS-01
Sun and ball-impact protection hood, 184 x 180 x 80 mm, stainless steel V2A (1.4301)
WS-04
Weather and sun protection hood, 130 x 180 x 135 mm, stainless steel V2A (1.4301)
DIP
DIP
1
2
OFF
OFF
O N
OFF
OFF
O N
O N
O N
DIP
6
O N
OFF
Display
standard
Temperature (switchable)
0...+50 °C ( default )
(MR)
–20...+80 °C
(MR)
–35...+75 °C
3
(A.H.)
–35...+35 °C
3
(A.H.)
(DP)
(DP)
(ENT.)
(4 x as above)
(4 x as above)
(4 x as above)
(4 x as above)
(4 x as above)
(4 x as above)
(4 x as above)
Switchable
measuring ranges
(adjustable)
r.H.:
0...100 % (default)
MR:
0...50 g ⁄ kg
MR:
0...80 g ⁄ kg
3
A.H.:
0...50 g ⁄ m
A.H.:
0...80 g ⁄ m
3
TP:
0...+50 °C
TP:
–20...+80 °C
ENT.:
0...85 kJ ⁄ kg
Possible variables:
(r.H.)
= relative humidity in % RH
(MR)
= mixture ratio in g ⁄ kg
(A.H.)
= absolute humidity in g ⁄ m
(TP)
= dew point in °C
(ENT.) = enthalpy in kJ ⁄ kg
Display
alternative output variables
DIP switches can be used to display an alternative output
variable instead of the standard display:
Absolute humidity in g ⁄ m³
Dew point in °C
Mixture ratio in g ⁄ kg
Enthalpy in kJ ⁄ kg
Output
Display
Humidity
Temperature
4...20 mA 4...20 mA
4...20 mA 4...20 mA
0 -10 V
0 -10 V
0 -10 V
0 -10 V
4...20 mA 4...20 mA
4...20 mA 4...20 mA
0 -10 V
0 -10 V
0 -10 V
0 -10 V
DIP
DIP
DIP
3
4
5
OFF
OFF
OFF
O N
OFF
OFF
OFF
O N
OFF
OFF
OFF
O N
O N
O N
OFF
O N
OFF
O N
OFF
O N
O N
O N
O N
O N
3
Item No.
1201- 3162-6000- 029
1201-3 162-6200- 029
1201- 3161-600 0-029
1201- 3161-620 0-029
1201- 1162-600 0-028
1201-1 162-6200- 028
1201- 1161-600 0-028
1201- 1161-620 0-028
7000-0050- 2200- 100
7100- 0040-2000- 000
7100- 0040-7000 -000

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis