Holding Register:
Ordnungs
Beschreibung der
Variable
Variable
40001
mode
40002
fan speed
40003
set point temperature
40004
on/off
40005
temperature lower limit
40006
temperature upper limit
40007
Power failure
40008
Key-lock
40009
Backlight delay
40010
change over temperature
cooling (2-pipe + external
temp. sensor)
40011
change over temperature
heating (2-pipe + external
temp. sensor)
40012
Fan coil type
40013
7day 4periods
programmable
40014
time of the first
temperature zone
40015
temperature setting of the
first temperature zone
40016
time of the second
temperature zone
40017
temperature setting of the
second temperature zone
40018
time of the third
temperature zone
40019
temperature setting of the
third temperature zone
40020
time of the fourth
temperature zone
40021
temperature setting of the
fourth temperature zone
40022
Individual passwords
setting
40023
Summer/winter time
40024
system time-- year
40025
system time--month
40026
system time--day
40027
system time-hour
40028
system time-minutes
40029
system time--seconds
40030
system week
40031
IR receiver
Thermokon Sensortechnik GmbH, Platanenweg 1, 35756 Mittenaar, Deutschland · Tel: 02778/6960-0 · Fax: -400 ·
lesen -
Einheit
schreiben
Read / Write
NC
Read / Write
NC
Read / Write
0.1℃
1-500(0x01F4),for example:265 and 26.5℃
Read / Write
NC
Read / Write
1℃
Read / Write
1℃
Read / Write
NC
Read / Write
NC
Read/Write
s
Read /Write
1℃
Read /Write
1℃
Read /Write
NC
2=cooling&heating 2-pipe 4=cooling&heating
Read /Write
NC
Read /Write
NC
Read /Write
1℃
Read /Write
NC
Read /Write
1℃
Read /Write
NC
Read /Write
1℃
Read /Write
NC
Read /Write
1℃
Read /Write
NC
Read /Write
NC
Read /Write
NC
Read /Write
NC
Read /Write
NC
Read /Write
NC
Read /Write
NC
Read /Write
NC
Read /Write
NC
Read /Write
NC
LCF_TOUCH_Modbus_V2.1_Datenblatt_de.docx © 2019
Varianten
1=cool,4=fan,8=heat,16=auto
2=low,4=medium,8=high,128=auto
0=stop,1=run
1-50(0x0032)
default=16℃
1-50(0x0032) default=30℃
0-keep off power on,1-Memo while the
power failure, 2-switch on while power on
Default=0
see parameter table: binary notation
Temp=16=0x10
Fan=8=0x08
Clock=4=0x04
Mode=2=0x02
ON/OFF=1=0x01
10-150s,default=15s
12-24,default=19℃
25-45,default=30℃
4-pipe ,6=cooling+elec-heater,default=2
0=forbidden,1=allowed ,default=0
hour:min,BCD code data format
e,g:08:30=0x0830
16-30,default=25℃
hour:min, BCD code data format
e,g:14:00=0x1400
16-30,default=26℃
hour:min,e,g:20:00=0x2000
16-30,default=27℃
hour:min, BCD code data format
e,g:02:00=0x0200
16-30,default=28℃
001-999,defaul=260
0=forbidden,1=allowed ,default=1
2000-2099,default=2015
01-12
01-31
00-23
00-59
00-59
1=Sun ,2=Mon ,3=Tue ,4=Wed 5=Thu
6=Fri 7=Sat
0=OFF, 1=ON
Stand: 27.02.2019
Register
Funktionscode
0x0000
0x000F
0x0001
0x03,00x06,0x10
0x0002
0x03,00x06,0x10
0x0003
0x03,00x06,0x10
0x0004
0x03,00x06,0x10
0x0005
0x03,00x06,0x10
0x0006
0x03,00x06,0x10
0x0007
0x03,00x06,0x10
0x0008
0x03,00x06,0x10
0x0009
0x03,00x06,0x10
0x000A
0x03,00x06,0x10
0x000B
0x03,00x06,0x10
0x000C
0x03,00x06,0x10
0x000D
0x03,00x06,0x10
0x000E
0x03,00x06,0x10
0x000F
0x03,00x06,0x10
0x0010
0x03,00x06,0x10
0x0011
0x03,00x06,0x10
0x0012
0x03,00x06,0x10
0x0013
0x03,00x06,0x10
0x0014
0x03,00x06,0x10
0x0015
0x03,00x06,0x10
0x0016
0x03,00x06,0x10
0x0017
0x03,00x06,0x10
0x0018
0x03,00x06,0x10
0x0019
0x03,00x06,0x10
0x001A
0x03,00x06,0x10
0x001B
0x03,00x06,0x10
0x001C
0x03,00x06,0x10
0x001D
0x03,00x06,0x10
0x001E
0x03,00x06,0x11