5.

Wiring

The following diagram shows the connection assignment of the DFA:
Terminal
Description
1
status (ext. LED)
2
connecting RCCB
3
disconnecting RCCB
4
tripping RCCB
5
+24 V
6
0 V
DC
7
Dupline+ (D+) optional
8
Dupline- (D-) optional
!
While so doing it must be ensured that all leads are dead.
The power supply of the DFA must not be realized via the switched RCCB.
20
4k7
1 2 3 4
9 10 11 12 13
24 V AC
(DC+)
DC
(DC-)
5 6 7 8
24 V AC/DC
1A
15
14
Terminal
9
10
11
12
13
14
15
16
A
B
C
D
16
Lx
N
Description
24 V
AC
24 V
AC
relay output: common pole
relay output: RCCB connected
relay output: RCCB disconnected
relay output: RCCB tripped
output: remote trip Lx
output: remote trip N