APPENDIX

Control Drawing 5106QU01
56
Control Drawing 5106QU01
Hazardous (Classified) Location
Class.I,.Division.1,.Group.A,B,C,D.
Class.I.,.Zone.0.and.1,.Group.IIC.
Class.II,.Division.1.Group.E,.F,.G
Intrinsically.safe.apparatus..
entity.parameters:.
Vmax..(Ui).≥..Vt.(Uo)
Imax..(Ii)....≥..It.(Io)
Pi..≥..Po
Ca.≥.C cable .+.Ci
La.≥.L cable. .+.Li
The.sum.of.capacitance.and.
inductance.of.cable.and.
intrinsic.safe.equipment.must.
be.less.or.equal.to.Ca.and.La.
5106B.Associated.apparatus.parameters
CH1
Terminals.44.to.41,42
CH2
Terminals.54.to.51,52
Vt..(Uo)
28.V
It...(Io)
93.mA
Po
0.65.W
IIC./.grp..A,.B IIB./.grp..C IIA./.grp.D IIC./.grp..A,.B
Ca.(Co)
0.06.μF
La..(Lo)
2.4.mH
Installation notes:
1).
The.maximum.nonhazardous.location.voltage.is.250VAC/DC..
2).
The.installation.shall.be.in.accordance.with.the.National.Electrical.Code..
.
NFPA.70,.Articles.504.and.505..
3).
The.terminals.of.the.two.individual.channels.shall.not.be.interconnected.in..any.
.
way..
4).
Install.in.Pollution.degree.2..or.better.
5).
Use.60./.75.°C.copper.conductors.with.wire.size.AWG:.(26.–.14)..
6).
Warning:.Substitution.of.components.may.impair.intrinsic.safety.
Nonhazardous
Associated.apparatus.
Galvanically.Isolated
31
33
44
14
mA
+
43
T
13
-
mA
42
12
+
-
41
11
CH1
54
24
mA
+
23
V
53
-
mA
52
22
+
21
-
51
5106B
CH2
Terminals.41.to.42
Terminals.51.to.52
10V
2.mA
5.mW
0.52.μF
1.72.μF
3.0.μF
12.mH
20.mH
1.0.H
+
+
57