USER INSTRUCTIONS
English
Programmable
Temperature Transmitter
GT 45000
Read these instructions before using the product and retain for future information.
GT 45000
► Before Startup
When operating the signal converter, certain parts
of the module can carry dangerous voltage!
Ignoring the warnings can lead to serious injury
and/or cause damage!
The signal converter should only be installed and
put into operation by qualified staff. The staff must
have studied the warnings in these operating
instructions thoroughly.
The signal converter may not be put into operation if
the housing is open.
In
applications
with
high
operating
voltages
sufficient distance and isolation as well as shock
protection must be ensured.
Safe and trouble-free operation of this device can
only be guaranteed if transport, storage and
installation are carried out correctly and operation
an maintenance are carried out with care.
Appropriate safety measures against electrostatic
discharge (ESD) should be taken during range
selection and assembly on the transmitter.
► Short description
The programmable transmitter is designed for operating various
industrial sensors. The measured values are converted into a
current or voltage signal. The configuration can be done either via
DIP switch for preference measuring ranges or extensive ranges via
an USB-interface with the PC configuration program GEORGINset.
The 3-way isolation guarantees reliable decoupling of the sensor
circuit from the processing circuit and prevents linked measurement
circuits from influencing each other. The auxiliary power can either
be supplied via the connection terminals or via the In-Rail-Bus
connector (see Accessories).
► Configuration and startup
Configuring with DIP switch
Use the DIP switches to configure the device, according to table.
Via the DIP switches you can select only a limited number of
sensors. A wider range of sensors you can select via software
configuration.
Configuring with software GEORGINset
Use the software GEORGINset to configure the device. Changes to
the configuration and parameterization data can be performed both
during operation with a connected measuring circuit and in a
disconnected state.
The GEORGINset software is available for download free of charge
at: www.georgin.com
The device is equipped with a programming socket on the front. Use
the GEORGINset USB Converter (Order no.: DZU1201) for
connecting the device to the PC. To change the configuration and
parameterization DIP switch S1- 1, 2, 3 have to be set ON!
Simulation Function
The simulation function with a stepped keystone signal on output
supports a fast and simple testing of cabling and connection of
downstream devices or measuring adjustment. Press the function
button located behind the front cover for longer than 3 seconds. The
simulation function will be indicated with a yellow LED (quick double off).
Output value:
Output
0 %
50 %
100 %
50%
Time
5 s
3 s
3 s
3 s
5 s
3 s
3 s
The stepped keystone signal is output continuously. Exit the
simulation function by pressing the button again for 3 seconds or
power off.
Teach-In Function for Potentiometer, Resistor and mV- Input
The Teach-In function can be used to teach in the start value and
end value. There are two ways of the Teach-In function:
● Automatic set up mode (Auto Teach-In)
● Manual Teach-In of the start and end value (Manual-Teach-In)
The taught-in values remain stored under the Teach-In setting. The
start value is 0 % and the end value is 100 % by default.
Starting the Teach-In Function
Use the function button located behind the front cover of the device
to teach in the device (use screw driver to push).
1. Configure the device using the DIP switches on the side of the device.
2. Press the function button for longer than 3 seconds.
The yellow LED will flash quickly
3. Auto Teach-In: Set input signal to both min and max range limits
as often as desired. Start value and end value will be
automatically determined and recorded.
or
Manual Teach-In: Set input signal to first range limit and press
the function button for around 0.5 seconds. Set second limit and
press the function button for around 0.5 seconds. This can be
repeated as often as required. The value of the last two
keystrokes will be stored for start value and end value.
Ending the Teach-In, Saving the Start Value and End Value
Press the function button for longer than 3 seconds. Release the
button when the yellow LED lights up constant. The values are
stored. The green LED indicates the successfully storage.
Ending the Teach-In without Saving the Start Value and End Value
Press the function button for longer than 6 seconds. Release the
button when the yellow LED starts to flash again after lit up
constant. The values are ignored and not stored.
or
Switch off the device. The values are not stored.
Teach-In Fault
If the span between the start value and the end value is too small,
the red LED will flash slowly after saving the values (configuration
error). In case of a fault, the Teach-In function must be performed
again in its entirety.
► Technical Data
Input
Sensor
Span
Error
min.
(max. of)
Pt100, Pt200, Pt500, Pt1000
50 K
< 0.1 K / 0.05 %
Ni100, Ni200, Ni500, Ni1000
KTY
50 K
< 0.1 K / 0.05 %
100 Ω
< 0.1 Ω / 0.02 %
Resistor
Sensor current / connection
0.2 mA / 4-wire, 3-wire, 2-wire
< 100 Ω per wire, manual compensation for 2-wire
Cable resistance
connection programmable
TC Sensor
E, J, K, L,
50 K / 100 K
< 0.3 K / 0.1 %
N, R, S, T, U / B, C, D
Cold junction
intern, extern Pt100, uncompensated, manual setting
compensation
(Error of cold junction compensation internal < 1.5 K)
±100 mV, ±1000 mV
5 mV, 50 mV
< 50 µV / 0.02 %
Poti 100 Ω to 50 kΩ
10 %
< 0.05 %
Output
Current
Output signal
0...20 mA
0...10 mA
4...20 mA
2...10 mA
≤ 12 V (600 Ω at 20 mA)
Load
Residual ripple
< 10 mV
rms
Transfer range
0 to 102.5 % (3.8 to 20.5 mA at output 4 to 20 mA)
Transfer characteristic rising / falling
Error signal
Sensor- / wire break, error signal programmable
3 s
General data
Transmission error
< 0.1 % full scale + input error
2)
Temperature coefficient
< 100 ppm/K
Measurement rate
4 / s
Test voltage
3 kV, 50 Hz, 1 min.
Input against output against power supply
3)
Working voltage
600 V AC/DC for overvoltage category II and
contamination class 2 acc. to EN 61010-1
(basic insulation)
Protection against
Protective Separation by reinforced insulation acc.
dangerous body
to EN 61010-1 up to 300 V AC/DC for overvoltage
3)
currents
category II and contamination class 2 between
input and output and power supply.
Ambient temperature
Operation
-25 °C to +70 °C (-13 to +158 °F)
Transport
-40 °C to +85 °C (-40 to +185 °F)
and storage
Power supply
24 V DC
16.8 V ... 31.2 V, approx. 0.8 W
4)
EMV
EN 61326-1
Construction
6.2 mm (0.244'') housing, protection type: IP 20
mounting on 35 mm DIN rail acc. to EN 60715
Connection
Solid:
0.5 mm
(captive plus-minus
Fine-stranded:
0.5 mm
clamp screws)
Stripped length: 6-8 mm / 0.28 in
Screw terminal torque 0.8 Nm / 7 lbf in
Weight
Approx. 70 g
1) Factory setting:
Input: Pt100, 0...100°C, 4-wire-sensor connection
Output: 0...20 mA, Characteristic rising, error signal 22 mA
2) Average TC in specified operating temperature range
3) As far as relevant the standards and rules mentioned above are considered
by development and production of our devices. In addition relevant assembly
rules are to be considered by installation of our devices in other equipment's.
For applications with high working voltages, take measures to prevent
accidental contact and make sure that there is sufficient distance or insulation
between adjacent situated devices.
4) Minor deviations possible during interference
► Dimensions
► Mounting, Electrical Connection
The transmitter is mounted on standard 35 mm DIN rail
ZERO
SPAN
Tk
< 50 ppm/K
< 50 ppm/K
< 50 ppm/K
< 50 ppm/K
< 50 ppm/K
► Order Information
< 50 ppm/K
Product
Voltage
Temperature Transmitter
0...10 V
0...5 V
2...10 V
1...5 V
Temperature Transmitter
≤ 5 mA (2 kΩ at 10 V)
In-Rail-Bus for power supply
WARRANTY
Régulateurs GEORGIN hereby warrants that the Product will
be free from defects in materials or workmanship for a period
of five (5) years from the date of delivery ("Limited
Warranty"). This Limited Warranty is limited to repair or
replacement at GEORGIN's option and is effective only for the
first end-user of the Product. This Limited Warranty applies
only if the Product:
1. is installed according to the instructions furnished by
GEORGIN;
2. is connected to a proper power supply;
3. is not misused or abused; and
4. there is no evidence of tampering, mishandling, neglect,
accidental damage, modification or repair without the
approval of GEORGIN or damage done to the Product by
anyone other than GEORGIN.
2
2
- 4 mm
/ AWG 20-12
Subject to change!
2
2
- 2.5 mm
/ AWG 20-14
Régulateurs GEORGIN
14-16 Rue Pierre Sémard
92320 - Châtillon
FRANCE
Téléphone :
+33 1 46 12 60 00
Fax :
+33 47 35 93 98
E-mail :
regulateurs@georgin.com
Internet : www.gorgin.com
Input /
Order No.
Output
programmable
GT 45000 S
programmable
GT 45000 B

Werbung

loading

Inhaltszusammenfassung für GEORGIN GT 45000

  • Seite 1 Transmission error < 0.1 % full scale + input error power off. replacement at GEORGIN’s option and is effective only for the Ignoring the warnings can lead to serious injury Temperature coefficient < 100 ppm/K first end-user of the Product.
  • Seite 2 Set the input and output ranges with DIP switches as indicated in the following table: Start Value End Value Input DIP S1 DIP S2 DIP S2 DIP S1 ● = on 9 10 °C °F Poti °C °F Poti °C °F Poti 1 2 3 4 5...
  • Seite 3 Übertragungsfehler < 0,1 % vom Endwert + Eingangsfehler Ausgang 0 % 50 % 100 % nach Wahl von GEORGIN beschränkt auf Reparatur oder Temperaturkoeffizient < 100 ppm/K ► Vor der Inbetriebnahme Austausch und gilt nur für den ersten Endbenutzer des...
  • Seite 4 Einstellung von Ein- und Ausgangsbereich mittels DIP-Schalter gemäß folgender Tabellen: Startwert Endwert Eingang DIP S1 DIP S2 DIP S2 DIP S1 ● = on 9 10 °C °F Poti °C °F Poti °C °F Poti 1 2 3 4 5 Pt100 ●...