11.
Under
Activities
management
Alarm conditions. Click Add
and enter the name of the alarm condition (e.g.:
"no showcase communication ").
12.
Choose the device and the alarm variable to be
checked.
13.
Click
to add the variable.
14.
Repeat to add the number of variables that need
to be checked.
15.
Click Add: the new condition is added to the list
of conditions.
Warning: the message area shows a notification
requiring the engine to be restarted and the direct
command to do so. This means boss needs to be
restarted to make the changes effective.
Note:
•
to set a single rule for all site alarm conditions,
select "All alarms".
•
set a rule for all alarm conditions based on priority,
select the priority to be managed under Priority.
16.
Under
Activities
management
Rules enter the name of the
rule (e.g.: "email no showcase communication").
17.
Choose the alarm condition or event (e.g.: "No
showcase communication ").
18.
Choose the time band in which the action is
enabled (e.g.: "dayshift weekdays").
19.
Choose the action (e.g.: "email to service")
20.
Define the delay for the action
21.
Enable the rule
22.
Click Add: the new rule is added to the list.
23.
Click Save.
24.
Restart the engine.
Alarm
and
event
Alarm
and
event
19
ENG
+040000260 - 1.0 - 22.09.2017