Alarm Messages

The control board can display specific alarm conditions. The table below shows the potential alarm messages on the
display.
Press ON/OFF to reset an alarm.
HIGH WATER TEMP
LOW WATER TEMP
LOW WATER FLOW
REMOTE POOL SPA
WATER THERM SHORT
WATER THERM OPEN
SUCTION TH SHORT
SUCTION TH OPEN
BROWNOUT
HIGH REFRIG
LOW REFRIG
FIVE ALARMS
SERIAL COMM LOST
Timer/ Counter Menu messages
Within the service menu it is possible to access diagnostic data reflecting the runtimes and number of cycles that a
specific output has been activated. Press the Up and Down arrows simultaneously.. Press the MENU SELECT button
repeatedly until the display shows
RUN TIMES/COUNTS
↑ OR ↓ TO VIEW
Use the up and down arrows to display the different messages.
Press POOL/SPA to exit this menu.
COMP RUN TIME
COMP CYCLES
COMP LOG TIME
FAN RUN TIME
FAN CYCLES
FAN LOG TIME
REV VLV RUN TIME
REV VLV CYCLES
REV VLV LOG TIME
FLT PMP RUN TIME
FLT PMP CYCLES
FLT PMP LOG TIME
DEFROST RUN TIME
DEFROST CYCLES
DEFROST LOG TIME
COMP WARRANTY
REV VLV WARRANTY
DEFROST WARRANTY
Water temperature is above 40°C
Water temperature is below 7°C
The switch sensing water flow is open.
Pool and Spa relay remote inputs are simultaneously energized.
Water temperature thermistor circuit shorted.
Water temperature thermistor circuit open.
Defrost thermistor circuit shorted
Defrost thermistor circuit open.
The 24 VAC supply voltage to the control board is low.
Refrigerant high pressure switch is open.
Refrigerant low pressure switch is open.
Indicates that 5 faults have occurred in one hour. This fault will automatically reset
in one hour or can be manually reset by pressing the ON/OFF button.
Problem with RS485 communication from IntelliPool
Displays current compressor runtime
Displays number of compressor cycles since last reset
Displays total compressor runtime since last reset
Displays current fan runtime
Displays number of fan cycles since last reset
Displays total fan runtime since last reset
Displays current reversing valve runtime
Displays number of reversing valve cycles since last reset
Displays total reversing valve runtime since last reset
Displays current autoset/extend relay runtime
Displays number of autoset/extend relay cycles since last reset
Displays total autoset/extend relay runtime since last reset
Displays current defrost runtime
Displays number of defrost cycles since last reset
Displays total defrost runtime since last reset
Displays total compressor runtime (cannot be reset)
Displays total reversing valve runtime (cannot be reset)
Displays total defrost runtime (cannot be reset)