Herunterladen Diese Seite drucken

Honeywell 013975 Montage, Anschluss, Anleitung Seite 3

Netz-/ladeteil 12 v dc / 8 ah

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Mounting and Connection
Instructions
Mains/charger unit 12 V DC / 8 Ah
Item no. 013975
1.
General
Fully electronic mains/charger unit.
- Voltage-stabilized, current limited
- Redundancy standby operation
- Recognition of defective batteries (via LED
indication)
- Accumulator capacity up to max. 8 Ah
- Installer safe design with all high voltage
electronics fully shrouded
- DIN rail mounting clip
When selecting the size of housing, pay
attention to the space required for the accumu-
lator.
2.
Notes to Mains connection
The power supply must be connected to the
mains with a separate fuse.
If the electrical installation has an earth-leakage
circuit breaker (Fl switch), the energy supply
must have its own earth-leakage circuit breaker.
The fuse and Fl switch should, if possible, be
within the security zone.
P00228-10-002-01
2014-03-06
If the energy supply is not part of the control
panel, it should be installed in the immediate
vicinity (without a space between) so that an
attack on the connection line is impossible
without causing mechanical damage to the
housing.
The control panel and power supply should, if
possible, be screwed together.
Users not belonging to the system should not
be connected to the mains voltage.
3.
Mounting
Attention Safety instructions
When performing installation work of any kind,
the unit must be de-energized.
The non-fused earth conductor from the electric
power circuit
must be connected to the PE
(GND) connector of the connection terminals of
the supply voltage.
The power supply line must be fixed when
connecting so that the clearance (4 mm) and
creep paths (6.4 mm) between the electronic
modules and/or their periphery and the power
supply line are not shorter than stipulated.
If the neutral line cannot be clearly identified, a
second protection must be available in the
electric power circuit so that 2-pole separation
from the electric circuit is possible.
4.
Functional description
Two independent control circuits are installed
on the mother-board.
- First control circuit:
Supplies the control panel.
- Output control panel supply
with fuse T2A.
- Second control circuit:
Serves as a charger for the accumulators.
The charging current is limited to 0.5 A.
D
GB
Subject to change
without notice

Werbung