NORDAC START (SK 135E / SK 175E) – Handbuch für Motorstarter
Size
valid
1 - 2
generally valid
Motor
group
installation
(Group fusing):
differing
data
CSA:
1)
( 7.2)
Pos : 57 /Allgemein/Allgemeing ültige M odul e/---------- Seitenumbruc h ---------- @ 1\mod_1329145698658_0.doc x @ 15888 @ @ 1
24
"Suitable For Use On A Circuit Capable Of Delivering Not More Than 100 000 rms Symmetrical
Amperes, 500 Volts Maximum" "When Protected by class RK5 Fuses or faster, rated ______
Amperes, and 500 Volts", as listed in
"Suitable For Use On A Circuit Capable Of Delivering Not More Than 100 000 rms Symmetrical
Amperes, 500 Volts Maximum" "When Protected by High-Interrupting Capacity, Current
Limiting Class CC, G, J, L, R, T, etc., as listed in
"Suitable For Use On A Circuit Capable Of Delivering Not More Than 65 000 rms Symmetrical
Amperes, 480 Volt maximum",
"When Protected by Circuit Breaker (inverse time trip type) in accordance with UL 489, rated
______ Amperes, and 480 Volts", as listed in
"Suitable For Use On A Circuit Capable Of Delivering Not More Than 100 000 rms Symmetrical
Amperes, 500 Volts Max., When Protected by internal device SK CU4-FUSE"
"Suitable for motor group installation on a circuit capable of delivering not more than 100 000
rms symmetrical amperes, 500 V max" "When Protected by class RK5 Fuses or faster, rated
30_Amperes and 500 Volts."
"Suitable for motor group installation on a circuit capable of delivering not more than 100 000
rms symmetrical amperes, 500 V max" "When Protected by High-Interrupting Capacity, Current
Limiting Class CC, G, J, L, R, T, etc. Fuses rated 30 Amperes"
"Suitable for motor group installation on a circuit capable of delivering not more than 65 000
rms symmetrical amperes, 480 V max" "When Protected by Circuit Breaker (inverse time trip
type) in accordance with UL 489, rated 30 Amperes and 500 Volts, 480 V min"
None differing data  equal to UL
description
1)
.
1)
.
1)
, Rated short circuit current min. 65 kA
BU 0135 de-4118