Function selection
Input voltage
Max. current consumption
Max. contact load
Max. bounce period of NC contact
Fuses (F1/F2)
Feedback current
Feedback voltage
Permitted wire diameter
Permitted operating temperature /
storage temperature
Permitted relative humidity
Protection class as per IEC 60529
Classes of equipment as per
IEC 60950
Material and color interface module
housing
Material and color surface-mount
housing
Dimensions
-
FLM-420-RHV-D (with DIN rail
adapter):
-
FLM-420-RHV-S:
Bosch Sicherheitssysteme GmbH
2 LEDs (1 x red, 1 x green)
FAN or RLHV function via rotary
switch
15 V DC to 33 V DC
17.15 mA
-
10 A at 120 V AC / 230 V AC /
24 V DC
-
6 A at 30 V DC
9 ms
10 A / 250 V; type TH, slow, high
breaking
max. 1 mA (EOL resistor R = 3.9 kΩ)
max. 30 V DC
2
0.6 - 3.3 mm
-20 °C to +50 °C / -25 °C to +80 °C
<96 %, non condensing
-
FLM-420-RHV-D: IP 30
-
FLM-420-RHV-S: IP 54
Class II equipment
PPO(Noryl), off-white (similar to
RAL 9002)
ABS/PC-Blend, signal white
(RAL 9003)
approx. 110 x 110 x 48 mm
approx. 126 x 126 x 71 mm
en