Herunterladen Inhalt Inhalt Diese Seite drucken

Komfovent Ping2 Installationsanleitung Seite 13

Vorschau ausblenden Andere Handbücher für Ping2:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 38
1. Data and time of Air Handling Unit (AHU)
2. IP address of Ping2, when units are connected to Ethernet network (see Picture 3a).
3. Modbus ID of AHU: 1-247, 254 (Picture 3b).
4. Parameters of RS485 interface (J3 socket): data transfer speed (9600, 19200, 38400, 57600) and data format
(see Table 1).
5. Language selection.
6. Flow measuring units selection: m
7. AHU name (max. 24 symbols)
8. Changing of login password (max. 24 symbols).
Table 1
CONNECTION PARAMETERS RESTORE
It's possible to restore the factory-set IP address and password. For this the cover of box should be opened and
the board removed. Further restore procedure is:
1. turn off the power supply of "Ping2" (remove J1 plug);
2. put the "Reset" jumper (4a Picture);
3. turn on the power supply and wait until LED will start to blink (Picture 4a);
4. turn off power supply again and remove the jumper;
5. restore power supply.
"Reset"
jumper
Following the above steps the connection parameters of "Ping2" will be restored to default (Picture 4b).
UAB AMALVA we reserve the right to make changes without prior notice.
/h, m
/s, l/s.
3
3
Modbus data transfer format
Format
Data bits
8E1
8
8N1
8
8E2
8
8N2
8
Default connection parameters
IP address
Subnet mask
Username
Password
Parity
stop bits
Even
None
Even
None
192.168.0.29
255.255.0.0
user
user
Picture 4b
1
1
2
2
LED
Picture 4a
13