Herunterladen Inhalt Inhalt Diese Seite drucken

Safety Guidelines; Application; Functional Description; Technical Data - Honeywell TM3400 Einbauanleitung

Thermostatischer wassermischer
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

1. Safety Guidelines

1. Follow the installation instructions.
2. Use the appliance
• according to its intended use
• in good condition
• with due regard to safety and risk of danger.
3. Note that the appliance is exclusively for use in the appli-
cations detailed in these installation instructions. Any other
use will not be considered to comply with requirements
and would invalidate the warranty.
4. Please take note that any assembly, commissioning,
servicing and adjustment work may only be carried out by
authorized persons.
5. Immediately rectify any malfunctions which may influence
safety.

2. Application

Standard thermostatic mixing valves TM3400/TM3410 are
used in domestic hot water central heating systems with or
without recirculation. The aim is to maintain a constant
temperature of the mixed water for users, by varying the
temperature of the hot water stored. Thermostatic mixing
valves also have applications in underfloor heating applica-
tions and in alternative energy systems, such as solar and
woodchip systems.

3. Functional description

The highly sensitive thermal element located in the outlet of
the mixing valve controls a plug which regulates the flow
proportions of cold and hot water in relation to the mixed hot
water setting selected.
4. Application
Medium
Water

5. Technical data

Hot water inlet temperature Max. 90 °C
Operating pressure
Setting ranges
Control accuracy
Differential pressure
Δp hot-cold water
Flow rate
Connection size
MU1H-1369GE23 R0511
Max. 10 bar
30...45 °C
Set during manufacture 40 °C
36...53 °C
Set during manufacture 48 °C
45...65 °C
Set during manufacture 55 °C
± 1 K
Max. 2 bar
see diagram
/
" - 2" (TM3400)
1
2
DN65 - DN80 (TM3410)
GB

6. Scope of delivery

The thermostatic mixing valve comprises:
• Housing
• Cut-off switch
• Thermostat

7. Options

Setting range 30...45 °C Set during manufacture 40 °C
TM3400.912 with external thread connections
TM3400.922 with external thread connections
TM3400.932 with external thread connections 1"
TM3400.942 with external thread connections 1
TM3400.952 with external thread connections 1
TM3400.962 with external thread connections 2"
TM3410.605 with flange connections DN65, PN10 VSM/DIN
TM3410.805 with flange connections DN80, PN10 VSM/DIN
Setting range 36...53 °C Set during manufacture 48 °C
TM3400.914 with external thread connections
TM3400.924 with external thread connections
TM3400.934 with external thread connections 1"
TM3400.944 with external thread connections 1
TM3400.954 with external thread connections 1
TM3400.964 with external thread connections 2"
TM3410.606 with flange connections DN65, PN10 VSM/DIN
TM3410.806 with flange connections DN80, PN10 VSM/DIN
Setting range 45...65 °C Set during manufacture 55 °C
TM3400.916 with external thread connections
TM3400.926 with external thread connections
TM3400.936 with external thread connections 1"
TM3400.946 with external thread connections 1
TM3400.956 with external thread connections 1
TM3400.966 with external thread connections 2"
TM3410.608 with flange connections DN65, PN10 VSM/DIN
TM3410.808 with flange connections DN80, PN10 VSM/DIN

8. Assembly

8.1 Installations Guidelines
• The thermostatic mixing valves can be installed in any
position
• With any connections to be welded, during welding
remove the mixer so as not to damage the thermostat and
seals
• It is recommended that interception valves are installed on
the connection ways to the mixer
• The polystyrene packaging may be used as insulation for
the valve
5
/
"
1
2
/
"
3
4
/
"
1
4
/
"
1
2
/
"
1
2
/
"
3
4
/
"
1
4
/
"
1
2
/
"
1
2
/
"
3
4
/
"
1
4
/
"
1
2
Honeywell GmbH