Herunterladen Diese Seite drucken

Honeywell Piezo Montage, Anschluss, Anleitung Seite 2

Innensirene bus-1

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Mounting and Connection Instructions
Piezo indoor siren BUS-1
Item no. 043060.17
General Information
The indoor siren is suitable for indoor acoustical alarms.
- The cables can be either surface or flush mounted.
- The loudness can be programmed at two levels: 74 dB(A) / 90 dB(A)
- Four different types of signals can be programmed.
Technical Data
Rated operating voltage
Operating voltage range
Current consumption at 12 V DC
in no-load operation
active, loundness level 90 dB(A) typ. 60 mA
Programmable loundness level
Programmable types of signal
Protection category acc. to DIN 40 050
(only for mounting with radius at top)
Environmental class in acc. with VdS
Operating temperature range:
Dimensions (W x H x D)
Colour
Mounting
An opening can be cut out for
cables when surface mounting at
the positions indicated by the
arrows.
After testing, cover the screw
openings in the housing cover
using the enclosed plastic seals.
Honeywell Security Group
Novar GmbH
Johannes-Mauthe-Straße 14
D-72458 Albstadt
www.honeywell.com/security/de
12 V DC
10 V to 15 V DC
typ. 4 mA
74 dB(A) and 90 dB(A)
1.) 330 Hz to 1200 Hz
Increasing sawtooth
2.) 1200 Hz to 500 Hz
Decreasing sawtooth as per
DIN 33 404
3.) 660 Hz / 900 Hz
3x switching per second
4.) 500 Hz to 1200 Hz
sinussoidal
IP 32
ll
-5 °C to +45 °C
85 x 87 x 34 mm
traffic white (similar to RAL 9016)
Rear housing
panel
Cable opening
in the housing
Holes for
attaching
Pull through cable
binder to prevent
tension
P02017-10-002-05
2011-08-05
© 2011 Novar GmbH
Dimensions
(mm)
Piezo
85
Programming
S2/2, S2/3 Types of signal
S2/1 Loundness level
S2
S1
3
2
1
ON
ON
BUS-1 user address
The DIP-switch S1 is used for setting the BUS-1 user address
(1 to 63).
The illustration above demonstrates the user address 5.
Loudness level
Loudness level
DIP-switch S2/1
Reduced l
OFF
Maximum
ON
Types of signal
DIP-switch S2
S2/2
S2/3
330-1200 Hz
OFF
OFF
OFF
ON
1200-500 Hz
ON
OFF
660/900 Hz
ON
ON
500-1200 Hz
Connection diagram
+12 V DC
Data
0 V
Control unit
LED system fault
Cover contact
For connecting use a shielded cable stranded
in pairs as shown above.
It is not permitted to attach a EOL resistor to
the BUS-1.
Subject to change
without notice
6
5
4
3
2
1
User
address
setting
ON
ON
32 16 8 4 2 1
Valence
oudness level
: ca. 74 dB(A)
loudness level
: ca. 90 dB(A)
Types of signal
Increasing sawtooth
Decreasing sawtooth as per DIN 33 404
3x switching per second
sinussoidal
BUS-1
Indoor siren
BUS-1
BUS-1
+12 V DC
Data
0 V

Werbung

loading