INSTALLATION

Maintenance Space Requirements
It is recommended to install the air handling unit in a separate room or on the ceiling insulated with a rubber mat
or dampers (4 Picture). The place for the unit should be selected with allowance for minimum access to the unit for
maintenance and service inspection. The minimum free space in front of the control panel should be not less than
700 mm. Air handling units can be also installed over ceiling. To hang unit use vibration dampers. Free access to
the unit should be projected in ceiling construction.
1. Holder
Unit holder is made of 2,5 mm galvanized steel sheets according to EN 10142.
Ductwork
The air flows in/out air handling unit through ductwork. We recommend using galvanized steel (Zn 275 gr/m
to ensure easy cleaning and durability. It is necessary to use the ductwork system with low air flow rate and small
pressure drop to have necessary air volume and low sound level and save the energy. The appropriate sound
attenuators will reduce the noise level of the fans in the premises.
Outdoor and exhaust ductwork should be insulated with 50–100 mm thickness insulation to avoid the con-
densation.
Note: temperature sensor B1 has to be mounted in the supply air duct under electric heater (see the functional
diagram in Control System Installation and Operation Manual). It is necessary to leave space in straight air duct
for sensor mounting and guarantee the space for maintenance and service work. Minimal space between the unit
and B1 sensor is the space of double air duct diameter.

Final Inspection

After installation of the unit, a thorough inspection should be carried out. This should include inspecting the inside
of the unit and removing debris and tools, which may have been left behind by on site contractors. Replace any
panels, which may have been removed and close all access doors, ensuring that the door sealing gaskets have
not been damaged.
UAB AMALVA we reserve the right to make changes without prior notice
Maintenance Space
Ductwork, steelwork and any other services should not be supported off
the unit.
1
Ceiling
4 Picture
) ductwork,
2
15