between zero ‘o’ and full power ‘F’.
Stage 4 - Set the Output Channel Addresses
Before the OUTPUT module can operate correctly as part of the Imagine
System, the Channel Address for each output must be defined.
The module is supplied with the output CHA set to address 251 and CHB
set to 252. These need to be changed according to the application:
Procedure
1. With the display showing Output Level Mode
(default), press and hold the two
left-hand buttons.
2. Wait for the display to change to Channel Address
Mode (approximately 1 second) then release both
buttons.
Note: The display will show the current
address for output CHA.
3. To change the address, press and hold either the top
left-hand button to
increase, or the bottom left-hand button
to decrease the number.
(To leave the address as it is, go to step 5.)
4. To store the new address shown, press
and hold both left-hand buttons until the display
briefly shows ‘888’ to confirm
that the new value has been stored in the module’s
memory.
5. To view the address for output CHB, momentarily
press either the top or
bottom right-hand buttons.
6. To change the address, press and hold either the top
right-hand button to
increase, or the bottom right-hand button
to decrease the number. (To leave the address, do
nothing - the display will
revert to Output Level Mode after 10 secs).
7. To store the new address shown, press and hold both
right-hand buttons until the display briefly shows
‘888’ to confirm the new value has been stored.
Note: The display will revert to Output Level Mode
after 10 seconds.
Document Ref. EPD02083 (02/02/04)