RESI-UI-2SW2L-RD
RESI Informatik & Automation GmbH, Altenmarkt 29, A-8551 Wies, Austria, Tel: +43-316-262062-0, Fax: +43-316-262062-66, Email: help@RESI.cc URL: www.RESI.cc
IMPORTANT: Before you start with the installation of the product, read the attached IMPORTANT SECURITY NOTES very carefully and follow all the herein given information very accurate!
Description:
Manual control and monitor module with 2 build-in switches and 2 LEDs (24Vdc, max. 20mA) in RED. Each switch offers three positions: LEFT-CENTER-RIGHT. A 18 pin removable terminal block for wiring of all
switches and LEDs. Contact rating of the switches with resistive load: max. 2A@250Vac, max. 5A@120Vac, max. 5A@28Vdc. 4 internally bridged 2 pin terminal blocks to distribute the power supply (max. 60Vdc, max.
4A). Module suitable to build up a DIN ISO 16484 and VDI 3814 compatible manual operator interface, Weight: 160g, Dimension (LxWxH): 72x110x62mm, Snap able onto a EN50022 DIN rail or wall mounting.
Manual:
Read the actual manual for our product very carefully! You will find the manual on our homepage
CLAMPS
RESI-UI-2SW2L-RD
Power supply
Bridged group of clamps to supply other modules with the input supply
L+
L+: All pins marked L+ are internally combined (bridged) Supply 0..60Vdc
M-
M-: All pins marked M- are internally combined (bridged) Ground of the supply
SWITCH A
Clamps for SWITCH A:
IN
IN: Supply voltage for switch, both clamps are connected internally
IN
LT: If the switch is in position LEFT, the supply voltage on clamp IN will be
LT
outputted to this pin. In every other switch position this contact will be open
RT
RT: If the switch is in position RIGHT, the supply voltage on clamp IN will be
outputted to this pin. In every other switch position this contact will be open
IN
IN LT RT
LED B
Clamps for LED B:
1
1: +24Vdc pin for LED (Anode)
2
2: GND pin for LED (Cathode)
A
K
1
2
SWITCH C
Clamps for SWITCH C:
IN
IN: Supply voltage for switch, both clamps are connected internally
IN
LT: If the switch is in position LEFT, the supply voltage on clamp IN will be
LT
outputted to this pin. In every other switch position this contact will be open
RT
RT: If the switch is in position RIGHT, the supply voltage on clamp IN will be
outputted to this pin. In every other switch position this contact will be open
IN
IN LT RT
LED D
Clamps for LED D:
1
1: +24Vdc pin for LED (Anode)
2
2: GND pin for LED (Cathode)
A
K
1
2
www.RESI.cc
Technical Data
Contact rating
L+, M- terminals
Voltage
Current
Type of terminal block
All L+ are internally bridged together
All M- are internally bridged together
Switches A, C
Number of switches
Switch positions
Voltage for switch
Current for switch
Clamps
LED B, D
Number of LEDs
LED color
LED Voltage
Strom pro LED
Power consumption per
LED
Clamps
Clamps
Clamp wire cross section
Tightening torque
EN
2A@250Vac
5A@120Vac
5A@28Vdc
2x
IN
IN LT RT
Storage temperature
max 60Vdc
Operating
Temperature
max 4A
Protection Class
4xremoveable 2pin
Humidity
terminal block in black
Dimensions LxWxH
Weight
Mounting
2
LEFT-CENTER-RIGHT
max 250Vac
max 28Vdc
With resistive load
max 2A@250Vac
max 5A@120Vac
max 5A@28Vdc
1 removable 18 pin
terminal block in black
2
RED
24Vdc
max 20mA
<0.5W
1 removable 18 pin
terminal block in black
max 1,5 mm²
max 0.5Nm
CE conformity
24Vdc
max. 20mA
A
K
1
2
-20...80 °C
0...60°C
IP20 (EN 60529)
25...90 % rH non-
condensing
72mm x 110mm x 62mm
160g
On DIN EN50022 rail or
wall mounting
Yes
loading