A704/899398
2017-08-31
MR-TO4
11083013
Montagehinweis für den Installateur
de
Mounting note for the installer
en
Notice d'installation pour l'installateur
fr
Open Energy Management Equipment 34TZ
de
Nur Kupferleiter verwenden
en
Use copper conductors only
Utiliser uniquement des fils de cuivre
fr
C1| Anschlussbild
Connection diagram
Raccordements
N
24 V AC /
230 V AC
L
43 44
33 34
24 V AC/DC
A1
A1
GND
A2
A2
B+
BUS B+
B+
A-
A-
BUS A-
13 14
23 24
C2|Prinzipbild
Principle diagram
Schéma de principe
13
A1/ +24V
24 V
14
A2/ GND
23
BUS B+
BUS A-
24
33
34
43
44
METZ CONNECT GmbH | Im Tal 2 | 78176 Blumberg | Germany
Phone +49 7702 533-0 | Fax +49 7702 533-433
Weitere Dokumentation siehe / additional documentation see / documentation supplémentaire voir www.metz-connect.com
de
DEUTSCH
A| Sicherheitshinweise
GEFAHR
Gefahr bedeutet, dass bei Nichtbeachtung Lebens-
gefahr besteht, schwere Körperverletzungen oder
erhebliche Sachschäden auftreten können.
WARNUNG
Für die Montage, Inbetriebnahme und den Einsatz
des Geräts sind die jeweils länderspezifisch gültigen
Arbeitsschutz-, Unfallverhütungs- und Sicherheits-
bestimmungen einzuhalten und folgendes zu
beachten:
• Facharbeiter oder Installateure werden darauf
hingewiesen, dass sie sich vor der Installation
oder Wartung der Geräte vorschriftsmäßig ent-
laden müssen.
• Montage-, Wartungs- und Installationsarbei-
ten an den Geräten dürfen grundsätzlich nur
durch qualifiziertes Fachpersonal durchgeführt
werden.
• Qualifiziertes Fachpersonal im Sinne dieser
Anleitung sind Personen, die mit den beschrie-
benen Geräten vertraut sind und über eine
ihrer Tätigkeit entsprechenenden Qualifikation
verfügen.
B| Beschreibung
Das Modbus Modul mit 4 digitalen Triac-Ausgängen wurde
für dezentrale Schaltaufgaben entwickelt. Es ist geeignet zum
Schalten von elektrischen Komponenten z. B. Relais, Schütze,
HLK-Ventile usw. Über einen Modbus-Master können die Aus-
gänge über Standard-Register geschalten werden. Zusätzlich
können die Ausgänge über Schalter am Gerät manuell über-
steuert werden. Die Einstellung der Moduladresse, Bitrate und
Parität erfolgt über zwei Drehschalter auf der Frontseite oder
per Software.
Geeignet zur dezentralen Montage auf Tragschiene TH35 nach
IEC 60715 in Elektroverteilern.
C| Technische Daten
Protokoll
Modbus RTU
Adressbereich
00 bis 99
Busschnittstelle
RS485 (Zweidrahtbus)
Übertragungsrate
1200 bis 115200 Bit/s
Betriebsspannung
24 V AC/DC ± 10 % (SELV)
Stromaufnahme
100 mA (AC) / 40 mA (DC)
Einschaltdauer relativ
100 %
Ausgang / Kontakte
4 x Digitalausgang (Triac)
Ausgang / Schaltspannung
24 V AC bis max. 250 V AC
Ausgang / Dauerstrom
0,5 A / Ausgang
Ausgang / Schaltstrom
0,8 A (kleiner 30 s)
Ausgang / Einschaltstrom
10 A (kleiner 20 ms)
Anzeige
LED grün, rot, gelb
Abmessungen B x H x T
35 x 69,3 x 60 mm
Gewicht
95 g
Betriebstemperaturbereich
-5 °C bis +55 °C
Lagertemperaturbereich
-20 °C bis +70 °C
Schutzart Gehäuse / Klemmen
IP40 / IP20
Beschreibung
LED Anzeige
vorhandene Betriebsspannung
Grüne LED
Empfangen eines gültigen Kommandos
Grüne LED
vom Master
erlischt kurz
eingestellte Adresse „0"
Rote LED
Kommunikationsfehler, Parity-ERROR
Rote LED
Kommunikationsfehler, CRC-ERROR
Rote LED
Kommunikationsfehler, Framing-ERROR
Rote LED
unvollständige Frames
Rote LED
Nicht empfangenes Kommando
Rote LED
(bei Ausgangsmodulen)
Ausgang aktiv
Gelbe LED
HINWEIS
Zusätzliche Informationen, Dokumenta-
tionen und das Modbus Konfigurations-Tool
stehen zum Download unter
www.metz-connect.com bereit.
en
ENGLISH
A| Safety instructions
DANGER
Danger means that non-observance may cause
risk of life, grievous bodily harm or heavy material
damage.
WARNING
Follow the applicable country-specific safety at
work rules, the regulations for the prevention of
accidents and safety regulations when mounting,
bringing into service and using the device and
observe the following:
• Technicians and/or installers are informed that
they have to electrically discharge themselves as
prescribed before installation or maintenance of
the devices.
• Only qualified personnel is allowed to do moun-
ting, maintenance and installation work on the
devices.
• Qualified personnel in the sende of these inst-
ructions are persons who are well versed in the
use and installation of such devices and who
possess the necessary qualification for their job.
B| Description
The Modbus module with 4 digital triac outputs was developed
for decentralized switching tasks. It is suitable for switching
electrical components, such as relays, contactors, HVAC valves,
etc. The outputs can be switched by means of standard regis-
ters via a Modbus master. In addition, the outputs can be over-
ridden manually by means of switches on the device. Module
address, bit rate and parity are set with two rotary switches on
the front or by software.
Suitable for decentralized mounting on DIN TH35 rail according
to IEC 60715 in electrical distribution cabinets.
C| Technical Data
Protocol
Modbus RTU
Address range
00 to 99
Bus interface
RS485 (two-wire bus)
Transmission rate
1200 to 115200 bit/s
Operating voltage
24 V AC/DC ± 10 % (SELV)
Current consumption
100 mA (AC) / 40 mA (DC)
Relative duty cycle
100 %
Output / contacts
4 digital outputs (triac)
Output / switching voltage
24 V AC up to max. 250 V AC
Output / continuous current
0.5 A / output
Output / switching current
0.8 A (less than 30 s)
Output / switch-on current
10 A (less than 20 ms)
Display
Green, red and yellow LED
Dimensions (W x H x D)
35 x 69.3 x 60 mm
Weight
95 g
Operating temperature range
-5 °C to +55 °C
Storage temperature range
-20 °C to +70 °C
Ingress protection
for housing / terminal blocks
IP40 / IP20
Description
LED display
Operating voltage is present
Green LED
Reception of a valid command
Green LED turns
from the Master
off briefly
Address setting "0"
Red LED
Communication error, parity ERROR
Red LED
Communication error, CRC ERROR
Red LED
Communication error, framing ERROR
Red LED
Uncomplete frames
Red LED
Not received command
Red LED
(for output modules)
Output is active
Yellow LED
NOTE
Additional information, documentations
and the Modbus configuration tool are
available as download at
www.metz-connect.com
fr
FRANÇAIS
A| Avis de sécurité
DANGER
Danger signifie que de la non observation des
consignes peut entraîner un risque mortel ou des
dommages matériels importants.
AVERTISSEMENT
Pour le montage, la mise en service et l'utilisation
de l'appareil il faut respecter les règlements en
vigueur selon le pays concernant la protection au
travail, la prévention des accidents et la sécurité et
de respecter aussi les avis suivants :
• Des travailleur qualifiés ou installateurs sont
avertis qui'il est nécessaire de se décharger
correctement de l'électricité avant d'installer ou
d'entretenir l'appareil.
• Seul du personnel qualifié est autorisé à effectu-
er le montage et l'installation, voir paragraphe
personnel qualifié.
• Du personnel qualifié au sens de ces instructions
sont des personnes qui sont familiers avec les
appareils décrits et dont le qualifications pro-
fessionnelles sont en rapport avec leur travail.
B| Description
Le module Modbus avec 4 sorties triac numériques a été conçu
pour les tâches de commutation décentralisées. Il convient
pour commuter des composants électriques, par ex. des re-
lais, des contacteurs, des vannes CVC etc. Un maître Modbus
permet de commuter les sorties via des registres standards. De
plus, des interrupteurs sur l'appareil permettent de surmoduler
manuellement les sorties. L'adresse du module, le débit binaire
et la parité sont réglés par deux commutateurs rotatifs sur la
face avant ou par logiciel.
Convient au montage décentralisé sur rail DIN TH35 selon
IEC 60715 dans des répartiteurs électriques.
C| Données techniques
Protocole
Modbus RTU
Plage d'adresses
de 00 à 99
Interface bus
RS485 (bus à deux fils)
Vitesse de transmission
de 1 200 à 115 200 bit/s
Tension de service
24 V CA/CC ± 10 % (SELV)
Consommation électrique
100 mA (CA) / 40 mA (CC)
Taux de marche relatif
100 %
Sortie / contacts
4, sorties numériques (triac)
Sortie / tension de commutation 24 V CA à 250 V CA maxi.
Sortie / courant continu
0,5 A / sortie
Sortie / courant de commutation 0,8 A (inférieur à 30 s)
Sortie / courant de démarrage
10 A (inférieur à 20 ms)
Affichage
DEL verte, rouge, jaune
Dimensions L x H x P
35 x 69,3 x 60 mm
Poids
95 g
Plage des températures
de service
de -5 °C à +55 °C
Plage des températures
de stockage
de -20 °C à +70 °C
Indice de protection
boîtier/ borniers
IP40 / IP20
Description
Affichage
par DEL
Tension d'alimentation présente
DEL verte
Récéption d'une commande valable du
La DEL verte
Maître (Master)
s'éteint
brièvement
Adresse réglée « 0 »
DEL rouge
Erreur de communication, Parity ERROR
DEL rouge
Erreur de communication, CRC ERROR
DEL rouge
Erreur de communication,
DEL rouge
Framing ERROR
Trames (Frames) incomplèts
DEL rouge
Commande non reçue
DEL rouge
(pour les modules de sortie)
Sortie active
DEL jaune
NOTICE
Des informations et documentations
supplémentaires ainsi que l'outil de
configuration Modbus sont disponibles
pour téléchargement à
www.metz-connect.com